Plan Review Notes For Permit 17071002 |
Permit Number |
17071002 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-07-28 09:44:56 | FLORIDA BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED | | NFPA 70 2011 EDITION | | | | JAKE LEAHY | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | UNIT A SHOWS PANEL EITHER ABOVE KITCHEN COUNTER OR IN | | THE BATH ROOM NEITHER OF THESE ARE ACCEPTABLE. 240.24 | | | | UNIT C SHOWS LESS THAN 36" OF CLEANACE 110.26 | | | | SMOKE ALARMS WILL NEED TO BE ADDED. | | | | LAYOUT ON PLANS IS THIS EXISTING OR NEW? |
|