Plan Review Notes For Permit 17071000 |
Permit Number |
17071000 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2017-09-25 07:52:37 | BUILDING PLAN REVIEW | | 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 | | ADMINISTRATION | | | | CHRISTOPHER S. THROOP, C.B.O. | | PLANS EXAMINER, PX3169 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | | | 2ND REVIEW | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | THE FOLLOWING COMMENTS FROM 1ST REVIEW HAVE NOT BEEN | | ADDRESSED. | | | | 1. PROVIDE DESIGN WIND LOADS FOR EACH OPENING. | | 2. PROVIDE PRODUCT APPROVALS FOR EXTERIOR DOORS. | | 3. PROVIDE SCHEDULE FOR INSTALLATION OF OPENING | | PROTECTIVE DEVICES. | | | | FBC 107.3.5.3 - PROVIDE WIND DESIGN LOADS/DESIGN | | PRESSURES PURSUANT TO FBC-R301.2. | | | | FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | SPECIFICALLY, PROVIDE DOOR SUBMITTALS. | | | | | | | | | | | | |
|