2017-08-10 10:50:35 | CODES IN EFFECT: |
| FLORIDA BUILDING CODE 2014 5TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| EDITION |
| NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. RISER SHOWS 1/0 WIRE USED FOR A 200 AMP SERVICE. 1/0 |
| WIRE IS NOT RATED FOR 200 AMPS. PROVIDE CORRECTION. NEC |
| 215.2, 310.15; FBC RE3602.1 |
| 2. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| SERVICE. INCLUDE ALL AVAILABLE GROUNDING ELECTODES. NEC |
| 250.50, 250.94; FBC RE3609.3 |
| 3.PROVIDE AFCI PROTECTION TO CODE. NEC 210.12; FBC |
| RE3902.12, FBC 107.2.1 |
| 4. PROVIDE TAMPER RESISTANT OUTLETS TO CODE. NEC |
| 406.12; FBC RE4002.14 |
| 5.. WATER HEATER BREAKER IS TOO LARGE. PROVIDE |
| CORRECTION. NEC 422.13 |
| 6. AHU UNIT IS SHOWN BEING FED BY #6 WIRE. IS THIS |
| ROMEX, OR WIRING INSTALLED IN A CONDUIT? #6 ROMEX WIRE, |
| WHICH IS TYPICAL IN RESIDENTIAL WIRING, IS NOT RATED |
| FOR 60 AMPS. PROVIDE CORRECTION. NEC 334.80; FBC |
| RE3705.4.4 |
| 7. AHU UNIT APPEARS TO BE IN ATTIC. PROVIDE RECEPTACLE |
| OUTLET AT OR NEAR THE APPLIANCE. FBC RESIDENTIAL |
| M1305.1.3.1 |
| 8. CLOSET LIGHT IS NOT SPECIFIED. PROVIDE DETAIL OF |
| FIXTURE, OR NOTE TO COMPLY WITH CODE. NEC 410.16; FBC |
| RE4003.12 |
| 9. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| FBC EC R404.1 |
| 10. SMOLE ALARMS SHOULD BE LOCATED AT LEAST 3 FEET FROM |
| CEILING FAN BLADES OR MECHANICAL GRILL. PROVIDE |
| CORRECTION. NFPA 72, 11.8.3.5 |
| |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |