Plan Review Notes
Plan Review Notes For Permit 17070995
Permit Number 17070995
Review Stop E
Sequence Number 1
Notes
Date Text
2017-08-10 10:50:35CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. RISER SHOWS 1/0 WIRE USED FOR A 200 AMP SERVICE. 1/0
 WIRE IS NOT RATED FOR 200 AMPS. PROVIDE CORRECTION. NEC
 215.2, 310.15; FBC RE3602.1
 2. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. INCLUDE ALL AVAILABLE GROUNDING ELECTODES. NEC
 250.50, 250.94; FBC RE3609.3
 3.PROVIDE AFCI PROTECTION TO CODE. NEC 210.12; FBC
 RE3902.12, FBC 107.2.1
 4. PROVIDE TAMPER RESISTANT OUTLETS TO CODE. NEC
 406.12; FBC RE4002.14
 5.. WATER HEATER BREAKER IS TOO LARGE. PROVIDE
 CORRECTION. NEC 422.13
 6. AHU UNIT IS SHOWN BEING FED BY #6 WIRE. IS THIS
 ROMEX, OR WIRING INSTALLED IN A CONDUIT? #6 ROMEX WIRE,
 WHICH IS TYPICAL IN RESIDENTIAL WIRING, IS NOT RATED
 FOR 60 AMPS. PROVIDE CORRECTION. NEC 334.80; FBC
 RE3705.4.4
 7. AHU UNIT APPEARS TO BE IN ATTIC. PROVIDE RECEPTACLE
 OUTLET AT OR NEAR THE APPLIANCE. FBC RESIDENTIAL
 M1305.1.3.1
 8. CLOSET LIGHT IS NOT SPECIFIED. PROVIDE DETAIL OF
 FIXTURE, OR NOTE TO COMPLY WITH CODE. NEC 410.16; FBC
 RE4003.12
 9. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
 10. SMOLE ALARMS SHOULD BE LOCATED AT LEAST 3 FEET FROM
 CEILING FAN BLADES OR MECHANICAL GRILL. PROVIDE
 CORRECTION. NFPA 72, 11.8.3.5
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  