Plan Review Notes
Plan Review Notes For Permit 17070993
Permit Number 17070993
Review Stop E
Sequence Number 1
Notes
Date Text
2017-08-10 11:13:44CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. RISER SHOWS 1/0 WIRE USED FOR A 200 AMP SERVICE. 1/0
 WIRE IS NOT RATED FOR 200 AMPS. PROVIDE CORRECTION. NEC
 215.2, 310.15; FBC RE3602.1
 2. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. INCLUDE ALL AVAILABLE GROUNDING ELECTRODES.
 NEC 250.50, 250.94; FBC RE3609.3
 3. NOTE # 2 REFERENCES THE 2008 NEC FOR AFCI
 PROTECTION. 2008 NEC IS NOT CURRENT CODE. PROVIDE
 CORRECTION. FBC PREFACE
 4. NOTE # 3 STATES ALL SLEEPING AREAS SHALL HAVE AFCI
 PROTECTION. THE CODE REQUIRES MORE THAN JUST SLEEPING
 AREAS TO HAVE AFCI PROTECTION. REVISE TO REFLECT CODE.
 NEC 210.12; FBC RE3902.12, FBC 107.2.1
 5. NOTE # 4 REFERENCES THE 2008 NEC, SECTION 406.11 FOR
 TAMPER RESISTANT OUTLETS. PROVIDE CORRECTION. NEC
 406.12; FBC RE4002.14
 6. WATER HEATER BREAKER IS TOO LARGE. PROVIDE
 CORRECTION. NEC 422.13
 7. AHU UNIT IS SHOWN BEING FED BY #6 WIRE. IS THIS
 ROMEX, OR WIRING INSTALLED IN A CONDUIT? #6 ROMEX WIRE,
 WHICH IS TYPICAL IN RESIDENTIAL WIRING, IS NOT RATED
 FOR 60 AMPS. PROVIDE CORRECTION. NEC 334.80; FBC
 RE3705.4.4
 8. AHU UNIT APPEARS TO BE IN ATTIC. PROVIDE OUTLET AT
 OR NEAR THE APPLIANCE. FBC RESIDENTIAL M1305.1.3.1
 9. CLOSET LIGHT IS NOT SPECIFIED. PROVIDE DETAIL OF
 FIXTURE, OR NOTE TO COMPLY WITH CODE. NEC 410.16; FBC
 RE4003.12
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  