Plan Review Notes
Plan Review Notes For Permit 17070952
Permit Number 17070952
Review Stop E
Sequence Number 1
Notes
Date Text
2017-08-08 10:25:53CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLAN SHOWS LOCATION OF SMOKE ALARMS CLOSE TO CEILING
 FANS AND MECHANICAL SUPPLY AIR DUCTS. PROVIDE
 CORRECTION SO THAT SMOKE ALARM LOCATION ARE AT LEAST 3
 FEET FROM EACH FAN OR MECHANICAL GRILL. NFPA 72,
 11.8.3.5
 2. PLAN HAS 3 DIFFERENT NOTES ON TAMPER RESISTANT
 RECEPTACLES. 2 OF THOSE NOTES REFERENCE THE WRONG CODE
 SECTION (406.11) AND 1 OF THEM REFERENCES THE 2008 NEC,
 WHICH IS NOT THE CURRENT CODE. PLEASE REMOVE AND/OR
 CORRECT REDUNDANT NOTES. NEC 406.12; FBC RE4002.14
 3. PANEL SCHEDULE SHOWS THE AHU (WHICH REQUIRES A
 MINIMUM CIRCUIT AMPACITY OF 49 AMPS) ON A 50 AMP
 BREAKER WITH #8 WIRE. #8 ROMEX, WHICH IS TYPICAL IN
 HOUSE WIRING, IS NOT RATED FOR 49 AMPS. WILL THIS
 WIRING BE ROMEX, OR INSTALLED IN CONDUIT? PROVIDE
 CLARIFICATION AND/OR CORRECTION. NEC 334.80; FBC
 RE3705.4.4
 4. FOR DWELLING UNITS, ATTACHED GARAGES, AND DETACHED
 GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL
 SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED ON
 THE EXTERIOR SIDE OF OUTDOOR ENTRANCES OR EXITS WITH
 GRADE LEVEL ACCESS. PROVIDE CORRECTION. NEC
 210.70(A)(2)(B), FBC RE3903.3
 5. PLEASE CLARIFY THE OUTSIDE LIGHT FIXTURE LOCATIONS.
 PLAN SHOWS WIRING GOING TO LIGHTS, BUT DOES NOT SHOW
 SOME OF THE FIXTURE LOCATIONS. FBC 107.2.1
 6. PROVIDE GFCI PROTECTED OUTLET IN POWDER BATH WITHIN
 3 FEET OF BASIN. NEC 210.52(D); FBC RE3901.6
 7. WILL THE AQUARIUM BE PLACED ATOP WALL SPACE THAT
 WOULD REQUIRE AN OUTLET? PROVIDE WALL SPACE OUTLET IF
 NECESSARY. NEC 210.52(A); FBC RE3901.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  