2017-08-10 08:44:26 | RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW |
| COMMENTS. |
| CODE: FBC 5TH EDITION (2014). |
| |
| 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH |
| COUNTY FOR IMPACT FEES ASSESSMENT (2300 N. JOG RD.). |
| BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID |
| RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF |
| THE UNIFIED LAND DEVELOPMENT CODE. |
| |
| 2- BUILDING IS LOCATED IN EXPOSURE "C" NOT "B" AS |
| REQUIRED BY SEC. R301.2.1.4 FBC-RESIDENTIAL, 5TH |
| EDITION (2014). REVISE DESIGN INFORMATION ON SHEET S1 |
| OR PROVIDE COMPLETE RATIONAL ANALYSIS FOR EACH WIND |
| DIRECTIONS. |
| |
| 3- REVISE ALL COMPONENTS AND CLADDING DESIGN PRESSURES |
| ON SHEET S1 AND A2 TO REFLECT DESIGN PRESSURES FOR |
| EXPOSURE "C" AS REQUIRED BY ITEM #2 ABOVE. SEC. |
| R301.2.1.4 FBC-RESIDENTIAL. |
| |
| 4- PROVIDE COMPLETE SPECIFICATIONS FOR THE DOOR LEADING |
| FROM THE GARAGE TO THE MAIN HOUSE SHOWING COMPLIANCE |
| WITH ALL THE REQUIREMENTS OF OPENING PROTECTION OF SEC. |
| R302.5.1 FBC-RESIDENTIAL. |
| |
| 5- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING |
| COMPLIANCE WITH THE ROOF VENTILATION AS REQUIRED BY |
| SEC. R806 FBC-RESIDENTIAL. |
| NOTE: IF DESIGNING AND UNVENTED ATTIC, THEN PROVIDE |
| COMPLETE DETAILS AND SPECIFICATIONS AS REQUIRED BY SEC. |
| R806.5 FBC-RESIDENTIAL. COORDINATE WITH PERSON WHO IS |
| PREPARING THE ENERGY CALCULATIONS TO AVOID |
| CONFLICTS/DELAYS. |
| |
| 6- ROOF FRAMING PLAN ON SHEET S3 IS MISSING INFORMATION |
| FOR THE BOSTON HIP FRAMING ABOVE THE GARAGE AREA. |
| REVISE ROOF FRAMING PLAN AS REQUIRED TO MATCH EXTERIOR |
| ELEVATIONS. SEC. R301.1 FBC-RESIDENTIAL. |
| |
| 7- MASTER BATHROOM IS SHOWING ONLY MECHANICAL |
| VENTILATION FOR THE WATER CLOSET COMPARTMENT. NEED TO |
| PROVIDE MECHANICAL VENTILATION FOR THE BATHROOM ALSO AS |
| REQUIRED BY SEC. R303.3 FBC-RESIDENTIAL. |
| NOTE: COORDINATE INFORMATION ON MECHANICAL AND |
| ELECTRICAL PLANS. . |
| |
| 8- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| INSTALLATION OF THE BAHAMA SHUTTERS SHOWN ON THE FRONT |
| ELEVATION. SEC. R301.1 FBC-RESIDENTIAL. |
| |
| 9- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| INSTALLATION OF THE COLONIAL SHUTTERS SHOWN ON THE |
| FRONT ELEVATION. SEC. R301.1 FBC-RESIDENTIAL. |
| |
| 10- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| INSTALLATION OF THE GUARDRAILS SHOWN ON THE FRONT |
| ELEVATION. SHOW COMPLIANCE WITH THE LIVE LOADS OF TABLE |
| R301.5 FBC-RESIDENTIAL. ALSO, SPECIFY THE GUARDRAIL |
| HEIGHT AND PICKETS SPACING. SEC. R312 FBC-RESIDENTIAL. |
| |
| 11- ENERGY CALCULATIONS SUBMITTED: |
| A) OWNER OR LEGALLY DESIGNATED AGENT TO CERTIFY AND |
| DATE AT THE BOTTOM OF FROM AS REQUIRED BY SEC. |
| R103.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| |
| B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| INCLUDING THE BUILDER'S NAME. SEC. R101.5.1.1.2 |
| FBC-ENERGY CONSERVATION. |
| |
| C) CONCRETE BLOCK WALL INSULATION SHOWN ON ITEM #9(A) |
| DOESN'T MATCH INSULATION VALUE SPECIFIED BY THE |
| ENGINEER OF RECORD ON PLANS. REVISE AS REQUIRED TO |
| MATCH. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| D) CEILING INSULATION INFORMATION ON ITEM #10 NEEDS TO |
| BE COORDINATED WITH REVISED PLANS. SEE ITEM #5 ABOVE. |
| COORDINATE TYPE AND INSULATION R-VALUE. ALSO, |
| COORDINATE IF ENGINEER OF RECORD IS DESIGNING A VENTED |
| OR UNVENTED ATTIC. SEE ITEM # 5 ABOVE. SEC. |
| R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| E) PROVIDE INFORMATION FOR THE HOT WATER SYSTEM ON ITEM |
| #14. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| F) REVISE ROOF TYPE ON PAGE 3 OF 5. PLANS SHOW TWO |
| BOSTON HIP ENDS. ADD INFORMATION AS REQUIRED. SEC. |
| R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| G) COORDINATE ATTIC AND CEILING INFORMATION SHOWN ON |
| PAGE 3 OF 5 WITH CEILING INFORMATION SHOWN ON ITEM #10 |
| ON PAGE 1 OF 5. COORDINATE WITH PLANS TO AVOID |
| CONFLICTS/DELAYS. COORDINATE ATTIC VENTING AND |
| INSULATION R-VALUE. SEC. R101.5.1.1.2 FBC-ENERGY |
| CONSERVATION. |
| |
| NOTE: LABEL FOR DOORS AND WINDOWS SHOWING THE U-FACTOR |
| AND SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS |
| WILL BE REQUIRED WHEN THE ENERGY CALCULATIONS DON'T USE |
| THE GLAZING DEFAULT FACTORS. |
| |
| 12- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| FAC 61G20-3.001 FOR: |
| A) FRENCH DOORS WITH SIDELITES AND TRANSOM ABOVE AS |
| SHOWN ON PLANS. |
| |
| B) SINGLE HUNG WINDOWS AS SHOWN ON PLANS. |
| |
| C) FIXED WINDOWS AS SHOWN ON PLANS. |
| |
| D) METAL ROOF AS SHOWN ON PLANS. NOTE: CLEARLY IDENTIFY |
| FASTENING METHOD TO VERIFY COMPLIANCE WITH THE |
| ENGINEER'S CALCULATED DESIGN PRESSURES. |
| |
| E) GARAGE OVERHEAD DOOR AS SHOWN ON PLANS. |
| |
| F) GARAGE OUTSIDE SWING DOOR AS SHOWN ON PLANS. |
| |
| G) JAMES HARDI PLANK AS SPECIFIED ON PLANS. |
| |
| H) PRECAST LINTELS AS SPECIFIED ON PLANS. |
| |
| 13- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| |
| |
| ******ENGINEER TO PROVIDE RESPONSE LETTER ADDRESSING |
| EACH COMMENT TO EXPEDITE THE REVIEW PROCESS. . |
| ***** PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| DRAWINGS. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD |
| DRAWINGS FOR REFERENCE.. |
| |