2017-08-10 08:44:26RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY FOR IMPACT FEES ASSESSMENT (2300 N. JOG RD.).
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- BUILDING IS LOCATED IN EXPOSURE "C" NOT "B" AS
 REQUIRED BY SEC. R301.2.1.4 FBC-RESIDENTIAL, 5TH
 EDITION (2014). REVISE DESIGN INFORMATION ON SHEET S1
 OR PROVIDE COMPLETE RATIONAL ANALYSIS FOR EACH WIND
 DIRECTIONS.
  
 3- REVISE ALL COMPONENTS AND CLADDING DESIGN PRESSURES
 ON SHEET S1 AND A2 TO REFLECT DESIGN PRESSURES FOR
 EXPOSURE "C" AS REQUIRED BY ITEM #2 ABOVE. SEC.
 R301.2.1.4 FBC-RESIDENTIAL.
  
 4- PROVIDE COMPLETE SPECIFICATIONS FOR THE DOOR LEADING
 FROM THE GARAGE TO THE MAIN HOUSE SHOWING COMPLIANCE
 WITH ALL THE REQUIREMENTS OF OPENING PROTECTION OF SEC.
 R302.5.1 FBC-RESIDENTIAL.
  
 5- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING
 COMPLIANCE WITH THE ROOF VENTILATION AS REQUIRED BY
 SEC. R806 FBC-RESIDENTIAL.
 NOTE: IF DESIGNING AND UNVENTED ATTIC, THEN PROVIDE
 COMPLETE DETAILS AND SPECIFICATIONS AS REQUIRED BY SEC.
 R806.5 FBC-RESIDENTIAL. COORDINATE WITH PERSON WHO IS
 PREPARING THE ENERGY CALCULATIONS TO AVOID
 CONFLICTS/DELAYS.
  
 6- ROOF FRAMING PLAN ON SHEET S3 IS MISSING INFORMATION
 FOR THE BOSTON HIP FRAMING ABOVE THE GARAGE AREA.
 REVISE ROOF FRAMING PLAN AS REQUIRED TO MATCH EXTERIOR
 ELEVATIONS. SEC. R301.1 FBC-RESIDENTIAL.
  
 7- MASTER BATHROOM IS SHOWING ONLY MECHANICAL
 VENTILATION FOR THE WATER CLOSET COMPARTMENT. NEED TO
 PROVIDE MECHANICAL VENTILATION FOR THE BATHROOM ALSO AS
 REQUIRED BY SEC. R303.3 FBC-RESIDENTIAL.
 NOTE: COORDINATE INFORMATION ON MECHANICAL AND
 ELECTRICAL PLANS. .
  
 8- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 INSTALLATION OF THE BAHAMA SHUTTERS SHOWN ON THE FRONT
 ELEVATION. SEC. R301.1 FBC-RESIDENTIAL.
  
 9- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 INSTALLATION OF THE COLONIAL SHUTTERS SHOWN ON THE
 FRONT ELEVATION. SEC. R301.1 FBC-RESIDENTIAL.
  
 10- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 INSTALLATION OF THE GUARDRAILS SHOWN ON THE FRONT
 ELEVATION. SHOW COMPLIANCE WITH THE LIVE LOADS OF TABLE
 R301.5 FBC-RESIDENTIAL. ALSO, SPECIFY THE GUARDRAIL
 HEIGHT AND PICKETS SPACING. SEC. R312 FBC-RESIDENTIAL.
  
 11- ENERGY CALCULATIONS SUBMITTED:
 A) OWNER OR LEGALLY DESIGNATED AGENT TO CERTIFY AND
 DATE AT THE BOTTOM OF FROM AS REQUIRED BY SEC.
 R103.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING THE BUILDER'S NAME. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 C) CONCRETE BLOCK WALL INSULATION SHOWN ON ITEM #9(A)
 DOESN'T MATCH INSULATION VALUE SPECIFIED BY THE
 ENGINEER OF RECORD ON PLANS. REVISE AS REQUIRED TO
 MATCH. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 D) CEILING INSULATION INFORMATION ON ITEM #10 NEEDS TO
 BE COORDINATED WITH REVISED PLANS. SEE ITEM #5 ABOVE.
 COORDINATE TYPE AND INSULATION R-VALUE. ALSO,
 COORDINATE IF ENGINEER OF RECORD IS DESIGNING A VENTED
 OR UNVENTED ATTIC. SEE ITEM # 5 ABOVE. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 E) PROVIDE INFORMATION FOR THE HOT WATER SYSTEM ON ITEM
 #14. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 F) REVISE ROOF TYPE ON PAGE 3 OF 5. PLANS SHOW TWO
 BOSTON HIP ENDS. ADD INFORMATION AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 G) COORDINATE ATTIC AND CEILING INFORMATION SHOWN ON
 PAGE 3 OF 5 WITH CEILING INFORMATION SHOWN ON ITEM #10
 ON PAGE 1 OF 5. COORDINATE WITH PLANS TO AVOID
 CONFLICTS/DELAYS. COORDINATE ATTIC VENTING AND
 INSULATION R-VALUE. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 NOTE: LABEL FOR DOORS AND WINDOWS SHOWING THE U-FACTOR
 AND SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS
 WILL BE REQUIRED WHEN THE ENERGY CALCULATIONS DON'T USE
 THE GLAZING DEFAULT FACTORS.
  
 12- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) FRENCH DOORS WITH SIDELITES AND TRANSOM ABOVE AS
 SHOWN ON PLANS.
  
 B) SINGLE HUNG WINDOWS AS SHOWN ON PLANS.
  
 C) FIXED WINDOWS AS SHOWN ON PLANS.
  
 D) METAL ROOF AS SHOWN ON PLANS. NOTE: CLEARLY IDENTIFY
 FASTENING METHOD TO VERIFY COMPLIANCE WITH THE
 ENGINEER'S CALCULATED DESIGN PRESSURES.
  
 E) GARAGE OVERHEAD DOOR AS SHOWN ON PLANS.
  
 F) GARAGE OUTSIDE SWING DOOR AS SHOWN ON PLANS.
  
 G) JAMES HARDI PLANK AS SPECIFIED ON PLANS.
  
 H) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 13- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
  
  
 ******ENGINEER TO PROVIDE RESPONSE LETTER ADDRESSING
 EACH COMMENT TO EXPEDITE THE REVIEW PROCESS. .
 ***** PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWINGS. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD
 DRAWINGS FOR REFERENCE..
  