Plan Review Notes
Plan Review Notes For Permit 17070924
Permit Number 17070924
Review Stop P
Sequence Number 2
Notes
Date Text
2017-08-22 06:46:29SHT 2 OF 4 - THE PIPING SCHEMATIC SHOWS 2 1/2 INCH
 BRANCH PIPING AND 2 INCH MAIN DRAIN PIPING BUT IN THE
 BOX ON THE SAME PAGE THE SUCTION BRANCH PIPING IS
 CALLED OUT AS 3 INCH AND THE SUCTION TRUNK PIPING IS
 CALLED OUT AS 2 INCH. CLARIFY. 2ND REQUEST.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  