Plan Review Notes For Permit 17070924 |
Permit Number |
17070924 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2017-08-22 06:46:29 | SHT 2 OF 4 - THE PIPING SCHEMATIC SHOWS 2 1/2 INCH | | BRANCH PIPING AND 2 INCH MAIN DRAIN PIPING BUT IN THE | | BOX ON THE SAME PAGE THE SUCTION BRANCH PIPING IS | | CALLED OUT AS 3 INCH AND THE SUCTION TRUNK PIPING IS | | CALLED OUT AS 2 INCH. CLARIFY. 2ND REQUEST. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | |
|