Plan Review Notes For Permit 17070871 |
Permit Number |
17070871 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-07-26 05:48:20 | 1) CITY RECORDS SHOW AN EXISTING GAS METER AND SYSTEM | | FOR THIS ADDRESS. THE BTU LOAD OF THE EXISTING GAS | | SYSTEM MUST BE ADDED INTO THE TOTAL BTU LOAD ON THE | | SYSTEM TO ENSURE THE EXISTING SYSTEM IS PROPERLY SIZED. | | IF UNDERSIZED, THE EXISTING SYSTEM MUST BE REDONE TO | | ENSURE A SAFE OPERATING SYSTEM. SUBMIT A GAS PIPING | | RISER DIAGRAM THAT SHOWS THE TYPE OF EXISTING | | APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE PIPE | | SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE | | DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT | | OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF | | THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN | | A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO | | 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE | | EXISTING APPLIANCES. FGC SECS. 401.4, 401.8, 402.1, | | 402.2, 402.3 OR FBCR SECS.G2412.4, G2412.8, G2413.1, | | G2413.2, G2413.3. | | 2) SUBMIT A FLOOR PLAN SHOWING THE LOCATION OF THE | | OUTDOOR BBQ. IF IT IS LOCATED UNDER A ROOF THEN A HOOD | | MAY BE REQD. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | | | |
|