2017-09-29 16:39:21BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- ARCHITECT TO REVISE THE DESIGN PRESSURES FOR THE
 OVERHEAD GARAGE DOOR ON SHEET A3.2 TO CORRESPOND TO
 EXPOSURE "D".
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR:
 A) BALCONY DECK UNDERLAYMENT. ARCHITECT TO SPECIFY
 BALCONY FLOOR FINISH. NOTE: NEED PRODUCT APPROVAL THAT
 IS DESIGNED TO BE USED WITH THE SPECIFIC DECK FINISH
 MATERIAL TO BE INSTALLED IN THIS HOUSE. IN ADDITION
 CLEARLY IDENTIFY SPECIFIC ASSEMBLY TO BE INSTALLED AND
 PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS IF
 REQUIRED.
 *****NOA 14-0529.02 IS GOOD ONLY FOR OPTIONS SHOWN ON
 TABLE 4 OF SAME NOA. AND FLORIDA PRODUCT APPROVAL
 FL17442-R1 IS NOT GOOD EITHER.
 B) OVERHEAD GARAGE DOOR THAT MEETS THE DESIGN PRESSURES
 CALCULATED BY THE ARCHITECT OF RECORD. COORDINATE WITH
 ITEM #1 ABOVE.
 C) SINGLE HUNG WINDOWS. NEED LARGE MISSILE IMPACT
 RESISTANT PRODUCT APPROVAL. NOA 15-0512.08 SUBMITTED IS
 FOR SMALL MISSILE IMPACT RESISTANT.
 D) WINDOW MULLIONS AS SHOWN ON PLANS. AND, SPECIFY
 MULLION SIZE.
 E) FIXED WINDOWS AS SPECIFIED ON PLANS.
 F) GUEST HOUSE EXTERIOR SWING DOOR AS SHOWN ON PLANS.
 3- ARCHITECT OF RECORD TO REVIEW AND APPROVE ABOVE
 PRODUCT APPROVALS.
 4- ENGINEER WHO PREPARED THE RAS 117 CALCULATIONS FOR
 THE MAIN HOUSE TO PROVIDE CALCULATIONS WITH ORIGINAL
 SEAL AND SIGNATURE (NOT COPY) AS REQUIRED BY CHAPTER
 471 F.S.