2017-08-23 10:29:06 | 1ST REVIEW: FBC 2014 5TH EDITION |
| |
| PLUMBING COMMENTS: |
| |
| 1. PLEAS SHOW COMPLIANCE WITH FBC ACC 604.7 DISPENSERS. |
| TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230 |
| MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO |
| THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE |
| DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48 |
| INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND |
| SHALL NOT BE LOCATED BEHIND GRAB BARS. DISPENSERS SHALL |
| NOT BE OF A TYPE THAT CONTROLS DELIVERY OR THAT DOES |
| NOT ALLOW CONTINUOUS PAPER FLOW. |
| |
| 2. PROVIDE NOT ON PLAN TO SHOW COMPLIANCE WITH FBC ACC |
| 604.6 FLUSH CONTROLS. |
| FLUSH CONTROLS SHALL BE HAND OPERATED OR AUTOMATIC. |
| HAND OPERATED FLUSH CONTROLS SHALL COMPLY WITH 309. |
| FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN SIDE OF THE |
| WATER CLOSET EXCEPT IN AMBULATORY ACCESSIBLE |
| COMPARTMENTS COMPLYING WITH 604.8.2 |
| |
| 3. THERE SHALL BE A CLEANOUT NEAR THE JUNCTION OF THE |
| BUILDING DRAIN AND THE BUILDING SEWER. PER FBC PL |
| 708.3.5 |
| |
| 4. A TRAP PRIMER IS REQUIRED ON FLOOR DRAINS AND ICE |
| MACHINE DRAIN. PER FBC PL 1002.4 |
| |
| 5. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES |
| AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET |
| FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND |
| VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN |
| APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT |
| CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5 |
| |
| 6. A BACKFLOW IS REQUIRED ON ICE MACHINE SUPPLY. PER |
| FBC PL 608.3 |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |