2017-09-18 11:40:49 | CODES IN EFFECT: |
| FLORIDA BUILDING CODE 2014 5TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| EDITION |
| NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| |
| PREVIOUS COMMENT NOT ADDRESSED SATISFACTORILY: |
| |
| 1. PROVIDE RECEPTACLE CONTROL REQUIRED BY FBC C401.2 |
| AND ASHREA 90.1: 8.4.2 THIS SHOULD COMPLY WITH THE |
| FOLLOWING: |
| |
| ASHRAE 90.1, 8.4.2: |
| |
| AUTOMATIC RECEPTACLE CONTROL. THE FOLLOWING SHALL BE |
| AUTOMATICALLY CONTROLLED: |
| A. AT LEAST 50% OF ALL 125-VOLT 15 AND 20 AMP |
| RECEPTACLES IN ALL PRIVATE OFFICES, CONFERENCE ROOMS, |
| ROOMS USED PRIMARILY FOR PRINTING AND/OR COPYING |
| FUNCTIONS, BREAK ROOMS, CLASSROOMS, AND INDIVIDUAL |
| WORKSTATIONS. |
| B. AT LEAST 25% OF BRANCH CIRCUIT FEEDERS INSTALLED FOR |
| MODULAR FURNITURE NOT SHOWN ON THE CONSTRUCTION |
| DOCUMENTS. |
| |
| THIS CONTROL SHALL FUNCTION ON: |
| A. A SCHEDULED BASIS USING A TIME-OF-DAY OPERATED |
| CONTROL DEVICE THAT TURNS RECEPTACLES OFF A SPECIFIC |
| PROGRAMMED TIMES ? AN INDEPENDENT PROGRAM SCHEDULE |
| SHALL BE PROVIDED FOR CONTROLLED AREAS OF NO MORE THAN |
| 5000 SQ. FT. AND NOT MORE THAN ONE FLOOR (THE OCCUPANT |
| SHALL BE ABLE TO MANUALLY OVERRIDE THE CONTROL DEVICE |
| FOR UP TO TWO HOURS), OR |
| B. AN OCCUPANT SENSOR THAT SHALL TURN RECEPTACLES OFF |
| WITHIN 20 MINUTES OF ALL OCCUPANTS LEAVING A SPACE, OR |
| C. AN AUTOMATED SIGNAL FROM ANOTHER CONTROL OR ALARM |
| SYSTEM THAT SHALL TURN RECEPTACLES OFF WITHIN 20 |
| MINUTES AFTER DETERMINING THAT THE AREA IS UNOCCUPIED. |
| |
| ALL CONTROLLED RECEPTACLES SHALL BE PERMANENTLY MARKED |
| TO VISUALLY DIFFERENTIATE THEM FROM UNCONTROLLED |
| RECEPTACLES AND ARE TO BE UNIFORMLY DISTRIBUTED |
| THROUGHOUT THE SPACE. |
| |
| PLUG IN DEVICES SHALL NOT BE USED TO COMPLY WITH |
| SECTION 8.4.2 |
| |
| EXCEPTIONS: RECEPTACLES FOR THE FOLLOWING SHALL NOT |
| REQUIRE AN AUTOMATIC CONTROL DEVICE: |
| |
| 1. RECEPTACLES SPECIFICALLY DESIGNATED FOR EQUIPMENT |
| REQUIRING CONTINUOUS OPERATION (24 HOURS/DAY, 365 |
| DAYS/YEAR). |
| 2. SPACES WHERE AN AUTOMATIC CONTROL WOULD ENDANGER THE |
| SAFETY OR SECURITY OF THE ROOM OR BUILDING OCCUPANTS. |
| |
| PROVIDE CORRECTION. FBC CE 405.7.1 |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |