Plan Review Notes
Plan Review Notes For Permit 17070813
Permit Number 17070813
Review Stop E
Sequence Number 1
Notes
Date Text
2017-08-15 13:19:50CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. PROVIDE RECEPTACLE CONTROL REQUIRED BY FBC C401.2
 AND ASHREA 90.1: 8.4.2
 2. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE
 PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE
 PERMITS AND DATA SPECIFICATION SHEET SUBMITTALS FOR ALL
 LOW VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE
 ALARM, CCTV, PHONE AND DATA, WIRELESS SYSTEMS, KITCHEN
 HOODS ETC. A NOTE WILL SUFFICE.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  