Plan Review Notes
Plan Review Notes For Permit 17070813
Permit Number 17070813
Review Stop B
Sequence Number 1
Notes
Date Text
2017-08-18 06:59:402014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17070813
 ADD: 300 CLEMATIS ST. SUITE: 2/ 2ND FLOOR
 CONT: BUILTMORE CONTRACTING
 TEL: 305-502-2464
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRIDAY AUGUST 18, 2017
 ACTION: DENIED
  
 1) SHEET 004_DDA A-2ND-A1.1.1. THE DOOR TO THE EXIT
 STAIRS CENTRAL TO THE BUILDING IS LABELED 234 BUT ON
 THE DOOR SCHEDULE THIS EXIT DOOR DOES NOT PROVIDE ANY
 INFORMATION AS TO THE SIZE AND FIRE RATING REQUIRED.
 SHEET 003_DDA-2ND-AD1.1 THE DEMO PLAN HAS A NOTE 3 FOR
 THIS DOOR. NOTE 3 IS THE CONTRACTOR SHALL REMOVE AND
 STOCKPILE AT THE OWNERS SELECTION FOR BUILDING OWNERS
 FUTURE USE ALL DOORS AND HARDWARE.
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 104.9.1 USED MATERIALS AND EQUIPMENT.
 THE USE OF USED, RECYCLED, OR RECLAIMED MATERIALS WHICH
 MEET THE REQUIREMENTS OF THIS CODE FOR NEW MATERIALS IS
 PERMITTED. USED
 EQUIPMENT AND DEVICES SHALL NOT BE REUSED UNLESS
 APPROVED BY THE BUILDING OFFICIAL.
 PLEASE PROVIDE THE FOR DOOR 234 IN THE DOOR SCHEDULE
 COMPLIANCE WITH 2014 FBC-B 1008.1.1 SIZE OF DOOR AND
 SECTION & TABLE 716.5 OPENING PROTECTIVES.
  
 2) SHEET 012 DDA-2ND-A3.0.2 SEE DETAIL B TRANSFER TYPE
 SHOWER PLEASE NOTE THE DETAIL SHOWS A GRAB BAR ONLY
 AGAINST THE BACK WALL. PLEASE REFER TO THE
 FBC-ACCESSIBILITY CODE TO FIGURE 608.3.1 FOR THE
 REQUIRED PLACEMENT OF GRAB BAR IN A TRANSFER TYPE
 SHOWER.
  
 3) SHEET 012 DDA-2ND-A3.0.2 DOES NOT PROVIDE HOW
 COMPLIANCE WITH SECTION 609.8 STRUCTURAL STRENGTH.
 609.8 STRUCTURAL STRENGTH.
 ALLOWABLE STRESSES SHALL NOT BE EXCEEDED FOR MATERIALS
 USED WHEN A VERTICAL OR HORIZONTAL FORCE OF 250 POUNDS
 IS APPLIED AT ANY POINT ON THE GRAB BAR, FASTENER,
 MOUNTING DEVICE, OR SUPPORTING STRUCTURE.
  
 4) SHEET 012 DDA-2ND-A3.0.2 DETAIL B SHOWS THE SEAT
 ABOUT 7 INCHES SHORT OF THE FRONT ENTRY WALL. CALIBRATE
 AND MEASURE THE DISTANCE. PLEASE SHOW COMPLIANCE WITH
 FBC-ACCESSIBILITY CODE 610.3 SHOWER COMPARTMENT SEATS
 IN TRANSFER-TYPE SHOWERS, THE SEAT SHALL EXTEND FROM
 THE BACK WALL TO A POINT WITHIN 3 INCHES OF THE
 COMPARTMENT ENTRY. THE TOP OF THE SEAT SHALL BE 17
 INCHES (430 MM) MINIMUM AND 19 INCHES MAXIMUM ABOVE THE
 BATHROOM FINISH FLOOR. SEATS SHALL COMPLY WITH 610.3.1
 OR 610.3.2. ALSO SEE FIGURE 610.3(B) L-SHAPED SEAT.
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  