Plan Review Notes For Permit 17070801 |
Permit Number |
17070801 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2017-09-26 11:34:29 | PLAN | | REVIEW COMMENTS | | | | 3RD REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) (PREVIOUS COMMENT) THE PRODUCT APPROVAL THAT WAS | | SUBMITTED FOR THE BUILT UP ROOF (NOA NO.:14-1030.01) | | WILL REQUIRE ENHANCED FASTENING IN ORDER TO MEET THE | | UPLIFT PRESSURES FOR ROOF ZONES 2 AND 3. THE FASTENING | | OPTION THAT YOU INDICATED ON PAGE 15 OF THE NOA HAS A | | MAXIMUM DESIGN PRESSURE OF -52.5 PSF. THE REQUIRED | | UPLIFT PRESSURES FOR ZONE 2 IS -63.6 PSF AND FOR ZONE 3 | | IS -95.7 PER SHEET S.3 OF THE APPROVED PLANS. SEE | | LIMITATION NUMBER 7 ON PAGE 31 AND SUBMIT TWO SETS OF | | SIGNED AND SEALED RAS 117 CALCULATIONS FOR ENHANCED | | FASTENING FOR THE PERIMETER AND CORNER AREAS OF THE | | ROOF. FBC - R301.2.1 | | | | 2) (PREVIOUS COMMENT) THE RAS 117 CALCULATIONS THAT | | WERE SUBMITTED ARE BASED ON NOA NO.13-1022.15 WHICH HAS | | BEEN SUPERCEDED BY NOA NO. 14-1030.01. THE SYSTEM AND | | FASTENING OPTION THAT YOU INDICATED ON THE PRODUCT | | APPROVAL THAT WAS SUBMITTED DOES NOT MATCH THE | | CALCULATIONS. PLEASE SUBMIT MATCHING DOCUMENTS. FBC | | 107.2.1 | | |
|