2017-08-22 15:25:57PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) (PREVIOUS COMMENT) THE PRODUCT APPROVAL THAT WAS
 SUBMITTED FOR THE BUILT UP ROOF (NOA NO.:14-1030.01)
 WILL REQUIRE ENHANCED FASTENING IN ORDER TO MEET THE
 UPLIFT PRESSURES FOR ROOF ZONES 2 AND 3. THE FASTENING
 OPTION THAT YOU INDICATED ON PAGE 15 OF THE NOA HAS A
 MAXIMUM DESIGN PRESSURE OF -52.5 PSF. THE REQUIRED
 UPLIFT PRESSURES FOR ZONE 2 IS -63.6 PSF AND FOR ZONE 3
 IS -95.7 PER SHEET S.3 OF THE APPROVED PLANS. SEE
 LIMITATION NUMBER 7 ON PAGE 31 AND SUBMIT TWO SETS OF
 SIGNED AND SEALED RAS 117 CALCULATIONS FOR ENHANCED
 FASTENING FOR THE PERIMETER AND CORNER AREAS OF THE
 ROOF. FBC - R301.2.1
  
 2) (NEW COMMENT) THE RAS 117 CALCULATIONS THAT WERE
 SUBMITTED ARE BASED ON NOA NO.13-1022.15 WHICH HAS BEEN
 SUPERCEDED BY NOA NO. 14-1030.01. THE SYSTEM AND
 FASTENING OPTION THAT YOU INDICATED ON THE PRODUCT
 APPROVAL THAT WAS SUBMITTED DOES NOT MATCH THE
 CALCULATIONS. PLEASE SUBMIT MATCHING DOCUMENTS. FBC
 107.2.1
  