Plan Review Notes For Permit 17070801 |
Permit Number |
17070801 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-07-21 18:03:58 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE | | BUILT UP ROOF (NOA NO.:14-1030.01) WILL REQUIRE | | ENHANCED FASTENING IN ORDER TO MEET THE UPLIFT | | PRESSURES FOR ROOF ZONES 2 AND 3. THE FASTENING OPTION | | THAT YOU INDICATED ON PAGE 15 OF THE NOA HAS A MAXIMUM | | DESIGN PRESSURE OF -52.5 PSF. THE REQUIRED UPLIFT | | PRESSURES FOR ZONE 2 IS -63.6 PSF AND FOR ZONE 3 IS | | -95.7 PER SHEET S.3 OF THE APPROVED PLANS. SEE | | LIMITATION NUMBER 7 ON PAGE 31 AND SUBMIT TWO SETS OF | | SIGNED AND SEALED RAS 117 CALCULATIONS FOR ENHANCED | | FASTENING FOR THE PERIMETER AND CORNER AREAS OF THE | | ROOF. FBC - R301.2.1 | | | | NOTE: THE LEDGER FASTENING DETAIL ON THE ROOF FRAMING | | PLAN IS APPROVED. | | |
|