2017-07-21 18:03:58PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE
 BUILT UP ROOF (NOA NO.:14-1030.01) WILL REQUIRE
 ENHANCED FASTENING IN ORDER TO MEET THE UPLIFT
 PRESSURES FOR ROOF ZONES 2 AND 3. THE FASTENING OPTION
 THAT YOU INDICATED ON PAGE 15 OF THE NOA HAS A MAXIMUM
 DESIGN PRESSURE OF -52.5 PSF. THE REQUIRED UPLIFT
 PRESSURES FOR ZONE 2 IS -63.6 PSF AND FOR ZONE 3 IS
 -95.7 PER SHEET S.3 OF THE APPROVED PLANS. SEE
 LIMITATION NUMBER 7 ON PAGE 31 AND SUBMIT TWO SETS OF
 SIGNED AND SEALED RAS 117 CALCULATIONS FOR ENHANCED
 FASTENING FOR THE PERIMETER AND CORNER AREAS OF THE
 ROOF. FBC - R301.2.1
  
 NOTE: THE LEDGER FASTENING DETAIL ON THE ROOF FRAMING
 PLAN IS APPROVED.
  