Plan Review Notes
Plan Review Notes For Permit 17070728
Permit Number 17070728
Review Stop E
Sequence Number 1
Notes
Date Text
2017-07-27 10:55:22CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLAN REFERENCES THE 2008 NEC, WHICH IS NOT THE
 CURRENT CODE. PROVIDE CORRECTION. FBC PREFACE
 2. PLEASE INDICATE WHAT IS NEW AND WHAT IS EXISTING ON
 PLAN. IF BATH GFCI IS NEW, SHOW ON A 20 AMP CIRCUIT PER
 CODE. NEC 210.11(C)(3); FBC 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  