2017-08-08 06:09:12 | 2014 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 17070726 |
| ADD: 400 N. FLAGLER DR. |
| CONT:BESSENROTH BUILDERS |
| TEL: 561-324-4871 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| DATE: TUES. AUGUST 08/2017 |
| ACTION: DENIED |
| |
| 1) TO BE COMPLETED BY BESSENROTH BUILDERS. |
| 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE |
| EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H) |
| ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C) |
| (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT |
| WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE |
| CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE. |
| FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE |
| DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR |
| NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE |
| PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD |
| HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND |
| PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER |
| ONE SHEET. |
| |
| |