Plan Review Notes For Permit 17070709 |
Permit Number |
17070709 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-07-27 09:59:34 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #17070709 | | 7/27/17 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) THE PALM BEACH COUNTY APPRAISERS REPORT INDICATES | | THE RESIDENCE HAS NEVER HAD AN AC SYSTEM, AND THERE IS | | NO RECORD OF AN ISSUED PERMIT FOR A SYSTEM IN THE CITY | | PERMIT FILES- PLEASE CORRECT THE PLAN TO INDICATE A NEW | | SYSTEM IS BEING INSTALLED. | | | | 2) PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN- SECTION | | 1078.2.1 WPB AMENDMENTS TO THE FBC. | | | | 3) SUBMIT COOLING AND HEATING CALCULATIONS FOR THE NEW | | AC SYSTEM- SECTION R403.6.1 FBC-14 ENERGY CONSERVATION. | | | | 4) REFER TO SECTION R101.4.5 AND SUBMIT AN ENERGY | | EFFICIENCY COMPLIANCE REPORT FOR THE NEW CONDITIONED | | SPACE. SEE TABLE R101.5.1 FOR COMPLAINCE FORMS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|