2017-07-21 08:13:59 | 2014 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 17070704 |
| ADD: 1701 S FLAGLER DR. SUITE 1708 |
| CONT: NEWMAN WINDOWS & DOORS |
| TEL: 561-640-1092 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: FRI. JULY 21/2017 |
| ACTION: DENIED |
| |
| 1) WITH BUILDINGS OVER 60 FEET IN HEIGHT THE BUILDING |
| CODE DOES NOT HAVE CHARTS TO REVIEW BY, THE WIND DESIGN |
| AND ASSOCIATED PRESSURES HAVE TO BE ENGINEERED USING |
| ASCE 7-10. THE ASSUMPTION FOR EXPOSURE IS CORRECT AS AN |
| EXPOSURE D. 2014 FBC-B 1609.1.1 DETERMINATION OF WIND |
| LOADS. WIND LOADS ON EVERY BUILDING OR STRUCTURE SHALL |
| BE DETERMINED IN ACCORDANCE WITH CHAPTERS 26 TO 30 OF |
| ASCE 7 (CHAPTER 30 IS COMPONENTS & CLADDING). |
| |
| 2) PROVIDE THE LOCATION OF UNIT 1708 IN RELATIONSHIP TO |
| THE OVERALL BUILDING TO DETERMINE IF THE UNIT OR |
| SLIDING GLASS DOORS IS IN WALL ZONE 4 OR 5. ADDITIONAL |
| INFORMATION IS REQUIRED 107.2.1.3. |
| |
| 3) THE CONTRACTOR HAS IDENTIFIED WITHIN THE PRODUCT |
| APPROVAL ON THE TECHNICAL SHEETS 7 WHICH SYSTEM IS TO |
| BE INSTALLED WITH A 3 INCH SILL. FOR 36 INCH DOOR |
| =80/-100 PSF, & FOR A 48 INCH DOOR = +80/-93.3 PSF. |
| COMPLIANCE WILL BE DETERMINED WITH COMPLIANCE OF |
| COMMENTS 1 & 2. |
| |
| 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |