Plan Review Notes For Permit 17070699 |
Permit Number |
17070699 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-07-21 12:39:15 | 1555 PALM BEACH LAKES BOULEVARD - #150-155 | | PERMIT #17070699 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | PLAN INDICATES CITY WATER SUPPLY ONLY. THIS BUILDING | | HAS A FIRE PUMP. PER NFPA 13 (2007 EDITION) SECTION | | 24.2.1.2, PORTIONS OF SYSTEMS NORMALLY SUBJECTED TO | | SYSTEM WORKING PRESSURES IN EXCESS OF 150 PSI SHALL BE | | TESTED AT A PRESSURE OF 50 PSI ABOVE SYSTEM WORKING | | PRESSURE AND SHALL MAINTAIN THAT PRESSURE WITHOUT LOSS | | FOR 2-HOURS. | | | | FOR SYSTEM PRESSURES EXCEEDING 100 PSI, ARMOVERS AND | | END OF BRANCH LINE PENDENT SPRINKLERS SHALL BE | | PROTECTED FROM UPWARD MOVEMENT. HANGERS SHALL BE | | LOCATED WITHIN 12-INCHES OF THE DROP ELBOW. INDICATE | | THE HANGER TYPE OR METHOD TO BE USED FOR RESTRAINING | | UPWARD MOVEMENT. | | | | PROVIDE HYDRAULIC CALCULATIONS SUPPORTING THE USE OF | | THE FLEXIBLE SPRINKLER DROPS AND THE ADDITIONAL | | FRICTION LOSS ASSOCIATED WITH THESE PRODUCTS. | | | | SUBMIT PRODUCT DATA FOR THE FLEXIBLE SPRINKLER DROPS | | PROPOSED TO BE INSTALLED. INDICATE IF THE DROPS ARE | | BRAIDED OR UNBRAIDED. | | | | INDICATE THE MAXIMUM LENGTH OF FLEXIBLE DROP TO BE | | USED. | | | | WESLEY JOLIN | | ASSISTANT FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | | | |
|