2017-07-21 12:39:151555 PALM BEACH LAKES BOULEVARD - #150-155
 PERMIT #17070699
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PLAN INDICATES CITY WATER SUPPLY ONLY. THIS BUILDING
 HAS A FIRE PUMP. PER NFPA 13 (2007 EDITION) SECTION
 24.2.1.2, PORTIONS OF SYSTEMS NORMALLY SUBJECTED TO
 SYSTEM WORKING PRESSURES IN EXCESS OF 150 PSI SHALL BE
 TESTED AT A PRESSURE OF 50 PSI ABOVE SYSTEM WORKING
 PRESSURE AND SHALL MAINTAIN THAT PRESSURE WITHOUT LOSS
 FOR 2-HOURS.
  
 FOR SYSTEM PRESSURES EXCEEDING 100 PSI, ARMOVERS AND
 END OF BRANCH LINE PENDENT SPRINKLERS SHALL BE
 PROTECTED FROM UPWARD MOVEMENT. HANGERS SHALL BE
 LOCATED WITHIN 12-INCHES OF THE DROP ELBOW. INDICATE
 THE HANGER TYPE OR METHOD TO BE USED FOR RESTRAINING
 UPWARD MOVEMENT.
  
 PROVIDE HYDRAULIC CALCULATIONS SUPPORTING THE USE OF
 THE FLEXIBLE SPRINKLER DROPS AND THE ADDITIONAL
 FRICTION LOSS ASSOCIATED WITH THESE PRODUCTS.
  
 SUBMIT PRODUCT DATA FOR THE FLEXIBLE SPRINKLER DROPS
 PROPOSED TO BE INSTALLED. INDICATE IF THE DROPS ARE
 BRAIDED OR UNBRAIDED.
  
 INDICATE THE MAXIMUM LENGTH OF FLEXIBLE DROP TO BE
 USED.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE