Plan Review Notes For Permit 17070636 |
Permit Number |
17070636 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-08-04 19:12:20 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY MECHANICAL | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) A MECHANICAL PERMIT APPLICATION WAS SUBMITTED. THE | | DESCRIPTION OF WORK ON THE APPLICATION IS TO REPLACE | | THE A/C AND GRILLS PER PLANS. THE PLANS THAT WERE | | SUBMITTED STATE THAT THERE IS NO MECHANICAL WORK. | | PLEASE CLARIFY. FBC 107.2.1 | | | | 2) PLEASE CLARIFY THE MECHANICAL SCOPE OF WORK AND | | SUBMIT HVAC PLANS AND ANY OTHER CONSTRUCTION DOCUMENTS | | THAT MAY BE REQUIRED. FBC - 107.3.5.3 | | |
|