Plan Review Notes
Plan Review Notes For Permit 17070636
Permit Number 17070636
Review Stop E
Sequence Number 1
Notes
Date Text
2017-08-01 12:36:01CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ADDRESS ON PLAN DOES NOT MATCH THE ADDRESS ON PERMIT
 APPLICATION. PROVIDE PLAN WITH CORRECT ADDRESS. FBC
 107.2.1
 2. PROVIDE AFCI PROTECTION FOR NEW SMOKE ALARMS SHOWN
 ON PLAN. A NOTE WILL SUFFICE. NEC 210.12
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  