Plan Review Notes
Plan Review Notes For Permit 17070621
Permit Number 17070621
Review Stop M
Sequence Number 1
Notes
Date Text
2017-08-15 16:54:291ST REVIEW FBC-2014 MECHANICAL , WPB AMENDMENTS TO THE
 FBC
 PERMIT #17070621
 8/15/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE DRAWING INDEX ON SHEET M-1 INDICATES HVAC PLANS
 FOR THE 1ST, 2ND, AND 3RD FLOORS, HOWEVER THE 1ST FLOOR
 IS NOT INCLUDED ON SHEET M-2.
  
 2) M-2: SHOW THE LOCATION OF THE 5-TON AIR HANDLER FOR
 AC 2-2 ON THE FLOOR PLAN.
  
 3) M-1: INCLUDE AC 3-2 AND MS-2 IN THE EQUIPMENT
 SCHEDULE ON M-1.
  
 4) M-2: PROVIDE RETURN AIR FROM THE 2ND FLOOR OFFICES
 #1-6- SECTION 601.5.
  
 5) M-2: PLEASE EXPLAIN THE REASON WHY THE THREE
 DIFFUSERS IN SPACE 203 ARE BEING CAPPED. HOW WILL AIR
 BE SUPPLIED TO THE NORTH SECTION OF THE SPACE?
  
 6) M-2: THE 2ND FLOOR PLAN APPEARS TO BE CUT OFF-
 PLEASE PROVIDE THE ENTIRE LAYOUT PLAN,
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  