2017-07-21 14:50:17 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| |
| 1) SHEET A 601 - THE IS A DOOR SCHEDULE INDICATING ONE |
| DOOR INVLOVED IN THE PROJECT, DOOR 100, ON THE FIRST |
| FLOOR STAIRWELL. THERE IS NOT INDICATIONS ON THE DOOR |
| SCHEDULE IF THE DOOR IS REQUIRED TO BE RATED, IS IT |
| EXISTING, THE TYPE OF HARDWARE, TYPE OF EXIT DEVICES, |
| ETC. |
| |
| PLEASE REVIEW, CLARIFY OR CORRECT. |
| |
| |
| |
| 2) SHEET AD 1.01 - DOOR 100 COULD NOT BE LOCATED OR |
| IDENTIFIED. THERE ARE NO NOTE CALL-OUTS INDICATING |
| REMOVING THIS DOOR, |
| |
| PLEASE REVIEW, CLARIFY OR CORRECT. |
| |
| |
| 3) SHEET A 1.0 - DOOR 100 COULD NOT BE LOCATED OR |
| IDENTIFIED. |
| |
| PLEASE REVIEW, CLARIFY OR CORRECT. |
| |
| |
| |
| 4) SHEET A 3.01 - THERE ARE NO INDICATIONS OF A |
| LIGHWEIGHT TRUSS SIGN. |
| |
| PER FLORIDA 69A-60.0081; NOTICE SIGNAGE IS REQUIRED FOR |
| STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE CONSTRUCTION. |
| ANY COMMERCIAL, INDUSTRIAL, OR ANY MULTIUNIT |
| RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE WHICH USES |
| HORIZONTAL OR VERTICAL LIGHT-FRAME TRUSS-TYPE |
| CONSTRUCTION IN ANY PORTION SHALL BE MARKED WITH A |
| MALTESE CROSS SIGN MEASURING 8 INCHES HORIZONTALLY AND |
| 8 INCHES VERTICALLY, OF A BRIGHT RED REFLECTIVE COLOR. |
| THE APPROVED SYMBOL SHALL BE PLACED WITHIN 24 INCHES TO |
| THE LEFT OF THE MAIN ENTRY DOOR. |
| 1. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE |
| MARKED WITH THE LETTER "R". |
| 2. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS |
| SHALL BE MARKED WITH THE LETTER "F". |
| 3. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF |
| SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F". |
| |
| |
| PLEASE PROVIDE AS APPLICABLE PER THE ROOF AND FLOOR |
| DESIGN. |
| |
| |
| |
| 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| |
| 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |