Plan Review Notes
Plan Review Notes For Permit 17070607
Permit Number 17070607
Review Stop G
Sequence Number 1
Notes
Date Text
2017-07-21 10:20:441) SHOW THE CORRESPONDING EHD NUMBER OF THE CSST FOR
 EACH PIPE SIZE. COMPLY WITH TABLE 402.4 (15), 402.4
 (18).
 2) SUBMIT THE MANUFACTURER'S SIZING TABLE FOR THE PS-II
 CSST. WPB AMEND. TO FBC SEC. 107.2.1, 2014 FBC-FUEL GAS
 SEC.404.2.
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. 2014 FBC-FUEL GAS SEC. 410.1.
 4) GAS APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION. FGC
 SEC.305.1, FBC-RES. SEC.G2408.1.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW