Plan Review Notes For Permit 17070607 |
Permit Number |
17070607 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-07-21 10:20:44 | 1) SHOW THE CORRESPONDING EHD NUMBER OF THE CSST FOR | | EACH PIPE SIZE. COMPLY WITH TABLE 402.4 (15), 402.4 | | (18). | | 2) SUBMIT THE MANUFACTURER'S SIZING TABLE FOR THE PS-II | | CSST. WPB AMEND. TO FBC SEC. 107.2.1, 2014 FBC-FUEL GAS | | SEC.404.2. | | 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE | | PRESSURE REGULATORS. 2014 FBC-FUEL GAS SEC. 410.1. | | 4) GAS APPLIANCES SHALL BE LISTED AND LABELED. THE | | INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT | | SHALL BE ONSITE AT THE TIME OF INSPECTION. FGC | | SEC.305.1, FBC-RES. SEC.G2408.1. | | | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | | | | | |
|