2017-07-25 08:49:42 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| |
| 1. ALTHOUGH NOT CLOUDED AS A CHANGE ON A2 AND RELATED |
| BUILDING SHEETS, IT APPEARS THAT AN ADDITIONAL ACU WAS |
| ADDED, AND THE LOCATION OF THE OTHER ACU CHANGED. THE |
| PLAN SHOWS AN ALLEY ON THAT SIDE OF THE BUILDING, BUT |
| WITH NO DIMENSIONS. |
| |
| CLOUD ALL CHANGES, AND REVISE PLAN TO SHOW WIDTH OF |
| "ALLEY". REVISE PLAN TO SHOW DIMENSIONS OF ACUS. REVISE |
| PLAN TO EITHER SHOW ALL DOORS ON THE ADJACENT BUILDING, |
| OR REVISE PLAN TO NOTE THAT THERE ARE NO DOORS ON THE |
| WALL OF THE ADJACENT BUILDING, FBC 107, FBC CHAPTER 10. |
| |
| ***OR*** |
| |
| IF THIS PAGE DOES NOT NEED TO BE CHANGED FOR ANY OTHER |
| REASON, THIS ITEM MAY BE ADDRESSED WITH A SIGNED AND |
| SEALED LETTER. STATE THAT THIS IS THE ONLY CHANGE, THAT |
| THERE ARE NO DOORS ON ADJACENT BUILDING, AND THAT |
| EXITING FOR ADJACENT BUILDING IS NOT AFFECTED. |
| |
| 2. PROVIDE A VALUE FOR THE ADDITIONAL WORK, FBC 109. |
| ADDITIONAL MECHANICAL WORK, ENTRY DOOR ARE INCLUDED IN |
| THIS REVISION. |
| |
| 3. PROVIDE A PRODUCT APPROVAL FOR THE PROPOSED NEW |
| DOOR, FBC 1609. |
| |
| 4. SHEET A4 WAS SUBMITTED, UNABLE TO LOCATE A CHANGE TO |
| THE PLAN, FBC 107. CLOUD AND NUMBER OR DIRECT AS TO |
| WHERE THE CHANGE(S) IS(ARE). |
| |