Plan Review Notes For Permit 17070560 |
Permit Number |
17070560 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-07-20 08:16:13 | 250 SOUTH AUSTRALIAN AVENUE - 13TH FLOOR | | PERMITS 17070559 & 17070560 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | NEED SEAL OF SIGNATURE OF A PROFESSIONAL ENGINEER PER | | FLORIDA STATUTE 633 AND FLORIDA BUILDING CODE | | SECTION105.3.1.2: | | PERSONNEL AS AUTHORIZED BY CHAPTER 633 FLORIDA | | STATUTES, MAY DESIGN A FIRE SPRINKLER SYSTEM OF 49 OR | | FEWER HEADS AND MAY DESIGN THE ALTERATION OF AN | | EXISTING FIRE SPRINKLER SYSTEM IF THE ALTERATION | | CONSISTS OF THE RELOCATION, ADDITION OR DELETION OF NOT | | MORE THAN 49 HEADS, NOTWITHSTANDING THE SIZE OF THE | | EXISTING FIRE SPRINKLER SYSTEM. | | | | SCOPE OF THIS PERMIT IS 50 SPRINKLERS. ADDITIONALLY, | | THE SAME SPRINKLER SYSTEM ON THE SAME FLOOR, SUPPLIED | | FROM THE SAME CORRIDOR IS BEING MODIFIED UNDER PERMIT | | 17070559. BOTH PLANS SHALL BE SIGNED AND SEALED. | | | | WESLEY JOLIN | | ASSISTANT FIRE MARSHAL | | WPB FIRE RESCUE | | [email protected] |
|