Plan Review Notes For Permit 17070554 |
Permit Number |
17070554 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-07-24 14:08:17 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE IS NO DOOR SCHEDULE. | | | | PLEASE PROVIDE A DOOR SCHEDULE TO INCLUDE, EXISTING, | | RE-USED AND NEW DOORS, INCLUDING HARDWARE. | | | | | | | | | | 2) THERE ARE TWO SEPARATE FIRE WALL TYPES INDICATED | | THAT MAY INCLUDE SOME TYPE CONSTRUCTION WORK TO THEM OR | | WITHIN THEM. HOWEVER, THERE IS NO LISTED FIRE WALL CALL | | OUT FOR PENETRATIONS OR RE-CONSTRUCTIONS DUE TO THE | | REMODEL. | | | | PLEASE REVIEW AND PROVIDE THE APPLICABLE LISTED FIRE | | WALL(S). | | | | | | | | | | 3) THERE IS NO INDICATION OF AN EXISTING FIRE ALARM OR | | FIRE SPRINKLER SYSTEM. | | | | PLEASE REVIEW EXISING CONDITIONS AND PROVIDE OF | | APPLICABLE NOTE AND/OR THE SUBMITTAL OF FUTURE SHOP | | DRAWINGS FOR THE WORK. | | | | | | | | | | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | | | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|