Plan Review Notes
Plan Review Notes For Permit 17070554
Permit Number 17070554
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-07-24 14:08:17THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS NO DOOR SCHEDULE.
  
 PLEASE PROVIDE A DOOR SCHEDULE TO INCLUDE, EXISTING,
 RE-USED AND NEW DOORS, INCLUDING HARDWARE.
  
  
  
  
 2) THERE ARE TWO SEPARATE FIRE WALL TYPES INDICATED
 THAT MAY INCLUDE SOME TYPE CONSTRUCTION WORK TO THEM OR
 WITHIN THEM. HOWEVER, THERE IS NO LISTED FIRE WALL CALL
 OUT FOR PENETRATIONS OR RE-CONSTRUCTIONS DUE TO THE
 REMODEL.
  
 PLEASE REVIEW AND PROVIDE THE APPLICABLE LISTED FIRE
 WALL(S).
  
  
  
  
 3) THERE IS NO INDICATION OF AN EXISTING FIRE ALARM OR
 FIRE SPRINKLER SYSTEM.
  
 PLEASE REVIEW EXISING CONDITIONS AND PROVIDE OF
 APPLICABLE NOTE AND/OR THE SUBMITTAL OF FUTURE SHOP
 DRAWINGS FOR THE WORK.
  
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  