Plan Review Notes For Permit 17070554 |
Permit Number |
17070554 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-07-25 12:36:53 | CODES IN EFFECT: | | FLORIDA BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | EDITION | | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. LOAD SUMMARY FOR WWA PROVIDED SHOWS C PHASE OF 600 | | AMP DISCONNECT OVERLOADED. PROVIDE CORRECTION. NEC | | 230.79 | | 2. CIRCUIT 17,19 IN PANEL A1 SHOWS THE DRYER WITH #12 | | WIRE ON A 30 AMP BREAKER. PROVIDE CORRECTION. NEC | | 240.4, 310.15(B)(16) | | 3. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1: | | 8.4.2. FBC C405.7.1 | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|