Plan Review Notes
Plan Review Notes For Permit 17070554
Permit Number 17070554
Review Stop E
Sequence Number 1
Notes
Date Text
2017-07-25 12:36:53CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. LOAD SUMMARY FOR WWA PROVIDED SHOWS C PHASE OF 600
 AMP DISCONNECT OVERLOADED. PROVIDE CORRECTION. NEC
 230.79
 2. CIRCUIT 17,19 IN PANEL A1 SHOWS THE DRYER WITH #12
 WIRE ON A 30 AMP BREAKER. PROVIDE CORRECTION. NEC
 240.4, 310.15(B)(16)
 3. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1:
 8.4.2. FBC C405.7.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  