Plan Review Notes
Plan Review Notes For Permit 17070538
Permit Number 17070538
Review Stop M
Sequence Number 3
Notes
Date Text
2017-09-29 19:03:49PLAN
 REVIEW COMMENTS
  
 3RD REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE ENERGY FORMS CONTAIN ERRORS AND DO NOT
 ACCURATELY REFLECT THE DATA THAT IS SHOWN ON THE PLANS.
 FBC 107.2.1
 - THERE IS ONLY ONE BEDROOM AND IT IS LOCATED ON THE
 SECOND FLOOR. THE FORM HAS THREE (3) BEDROOMS. ONE ONE
 THE FIRST FLOOR AND TWO ON THE SECOND FLOOR. THE FIRST
 FLOOR IS A GARAGE AND STORAGE AND THE SECOND FLOOR HAS
 ONLY ONE (1) BEDROOM.
 - THE PLANS DO NOT SHOW A WHOLE HOUSE FAN. HOWEVER, THE
 CREDIT FOR ONE IS LISTED ON THE FORMS. THE PLANS STATE
 THAT THIS STRUCTURE HAS AN UNVENTED ATTIC, SUBMIT
 DOCUMENTS THAT SHOW HOW THE REQUIREMENTS OF FBC ENERGY
 CONSERVATION R405.7.5 WILL BE MET.
 - THE WINDOW OPENINGS AND ORIENTATIONS LISTED ON THE
 FORMS DO MATCH THE ONES THAT ARE SHOWN ON THE PLANS.
 TWELVE (12) WINDOW OPENINGS ARE LISTED ON THE FORMS AND
 SIXTEEN (16) ARE SHOWN ON THE PLANS. PLEASE CORRECT FBC
 107.2.1 AND FBC ENERGY CONSERVATION R 101.5.1.1.1
 - THE OWNER / AGENT IS REQUIRED TO SIGN AND DATE THE
 ENERGY FORM 402. FBC ENERGY CONSERVATION R103.1.1.2
  