2017-09-13 16:15:57CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PREVIOUS COMMENT #2 NOT ADDRESSED SATISFACTORILY.
 ALL OUTLETS IN GARAGE MUST BE GFCI PROTECTED, INCLUDING
 GARAGE DOOR OPENER. PROVIDE CORRECTION. NEC 210.8; FBC
 RE3902.2
 2. PREVIOUS COMMENT #8 NOT ADDRESSED SATISFACTORILY.
 PROVIDE ACCURATE LOAD CALCULATION. IT IS NOT
 PERMISSIBLE TO APPLY DEMAND FACTORS TO PANEL G AND
 INCLUDE THAT TOTAL IN THE SERVICE CALCULATION WHICH
 ALSO APPLIES DEMAND FACTORS. ADD ALL LOADS TOGETHER
 BEFORE APPLYING DEMAND FACTORS. NEC 220; FBC RE3602.3
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER