2017-08-28 19:03:00PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THIS STRUCTURE IS LOCATED WITHIN 600 FEET OF THE
 INTRACOASTAL WATERWAY WHICH IS SURFACE ROUGHNESS D. IN
 THE WIND DESIGN TABLE ON SHEET A101, THE SURFACE
 ROUGHNESS IS LISTED AS B WHEN IT IS ACTUALLY D FOR THIS
 PROJECT AS STATED IN THE PREVIOUS SENTENCE. SEE FBC-R
 301.2.1.4 AND R 301.2.1.4.3.
  
 2) ON SHEET A104 THE ELEVATIONS AT THE BOTTOM OF THE
 SHEET ARE BOTH INCORRECTLY IDENTIFIED. THEY SHOULD BE
 THE PROPOSED WEST AND THE PROPOSED NORTH ELEVATIONS.
 PLEASE CORRECT. FBC 107.2.1
  
 3) THE PROPOSED ARMOR SCREEN HAS A MAXIMUM DESIGN
 PRESSURE OF -60 PSF AND ONE OF THE DOOR OPENINGS
 REQUIRES -61.0 PSF. THIS EXCEEDS THE ARMOR SCREEN
 DESIGN PRESSURE. FBC-R 301.2.1
  
 4) EXPLAIN HOW A PERSON WILL BE ABLE TO ENTER AND LEAVE
 THE DWELLING WITH THE ARMOR SCREEN INSTALLED OVER THE
 ONLY EGRESS DOOR TO THE SECOND STORY THAT IS LOCATED ON
 THE FIRST FLOOR. FBC-R310.4
  
  
  