Plan Review Notes
Plan Review Notes For Permit 17070538
Permit Number 17070538
Review Stop B
Sequence Number 1
Notes
Date Text
2017-08-03 10:59:02PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) ACCORDING TO THE FBC EXISTING BUILDING SECTION 505,
 THIS IS A LEVEL 3 ALTERATION.
  
 2) BASED ON THE PLANS THAT WERE SUBMITTED, THIS
 STRUCTURE HAS A MEAN ROOF HEIGHT OF 23 FEET AND IS
 LOCATED IN EXPOSURE CATEGORY "D" WITH A 175 MPH VULT
 WIND SPEED. PLEASE PROVIDE THE WINDSPEED DESIGN DATA ON
 THE PLANS. FBC-R301.2.1
  
 3) THE REQUIRED DESIGN PRESSURES FOR THE WINDOWS AND
 DOORS THAT ARE SPECIFIED ON THE PLANS APPEAR TO BE
 BASED ON EXPOSURE CATEGORY "C". PLEASE REVIEW AND
 ADJUST AS NECESSARY. FBC-R301.1
  
 4) THE REQUIRED DESIGN PRESSURES FOR THE NEW SECTIONAL
 GARAGE DOORS WERE NOT SPECIFIED ON THE PLANS. PLEASE
 SPECIFY THEM ON THE PLANS. FBC 107.2.1
  
 5) FBC-R314.3.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS.
  
 6) ON SHEET A104 THE WEST AND NORTH ELEVATIONS ARE BOTH
 INCORRECTLY IDENTIFIED AS EAST ELEVATIONS. PLEASE
 CORRECT. FBC 107.2.1
  
 7) PLEASE IDENTIFY THE REQUIRED EGRESS WINDOW FOR THE
 SECOND FLOOR BEDROOM ON THE PLANS. FBC-R310.1 EMERGENCY
 ESCAPE AND RESCUE REQUIRED. FBC-R310.1.1 MINIMUM
 OPENING AREA. ALL EMERGENCY ESCAPE AND RESCUE OPENINGS
 SHALL HAVE A MINIMUM NET CLEAR OPENING OF 5.7 SQUARE
 FEET
  
  
  
  
  
  