2017-08-03 10:59:02 | PLAN |
| REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC FIFTH EDITION (2014) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) ACCORDING TO THE FBC EXISTING BUILDING SECTION 505, |
| THIS IS A LEVEL 3 ALTERATION. |
| |
| 2) BASED ON THE PLANS THAT WERE SUBMITTED, THIS |
| STRUCTURE HAS A MEAN ROOF HEIGHT OF 23 FEET AND IS |
| LOCATED IN EXPOSURE CATEGORY "D" WITH A 175 MPH VULT |
| WIND SPEED. PLEASE PROVIDE THE WINDSPEED DESIGN DATA ON |
| THE PLANS. FBC-R301.2.1 |
| |
| 3) THE REQUIRED DESIGN PRESSURES FOR THE WINDOWS AND |
| DOORS THAT ARE SPECIFIED ON THE PLANS APPEAR TO BE |
| BASED ON EXPOSURE CATEGORY "C". PLEASE REVIEW AND |
| ADJUST AS NECESSARY. FBC-R301.1 |
| |
| 4) THE REQUIRED DESIGN PRESSURES FOR THE NEW SECTIONAL |
| GARAGE DOORS WERE NOT SPECIFIED ON THE PLANS. PLEASE |
| SPECIFY THEM ON THE PLANS. FBC 107.2.1 |
| |
| 5) FBC-R314.3.1 ALTERATIONS, REPAIRS AND ADDITIONS. |
| WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A |
| PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE |
| ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS |
| LOCATED AS REQUIRED FOR NEW DWELLINGS. |
| |
| 6) ON SHEET A104 THE WEST AND NORTH ELEVATIONS ARE BOTH |
| INCORRECTLY IDENTIFIED AS EAST ELEVATIONS. PLEASE |
| CORRECT. FBC 107.2.1 |
| |
| 7) PLEASE IDENTIFY THE REQUIRED EGRESS WINDOW FOR THE |
| SECOND FLOOR BEDROOM ON THE PLANS. FBC-R310.1 EMERGENCY |
| ESCAPE AND RESCUE REQUIRED. FBC-R310.1.1 MINIMUM |
| OPENING AREA. ALL EMERGENCY ESCAPE AND RESCUE OPENINGS |
| SHALL HAVE A MINIMUM NET CLEAR OPENING OF 5.7 SQUARE |
| FEET |
| |
| |
| |
| |
| |
| |