Plan Review Notes
Plan Review Notes For Permit 17070528
Permit Number 17070528
Review Stop M
Sequence Number 2
Notes
Date Text
2017-08-08 14:53:172ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17070528
 8/8/17
  
 1) AS PREVIOUSLY REQUESTED IN THE FIRST REVIEW, PROVIDE
 VERIFICATION THAT THE THE NEW COOLING TOWERS ARE LISTED
 IN ACCORDANCE WITH UL 1995.
  
 2) CLARIFY IF THE BOILER REPLACEMENT NOTED ON SHEET M1
 IS TO BE INCLUDED IN THIS PERMIT, AND IF SO, PROVIDE
 DRAWINGS AND DETAILS, AND INCREASE THE VALUE OF THE
 PERMIT.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER