2017-07-18 10:08:571ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17070528
 7/18/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE VERIFICATION THAT THE COOLING TOWERS ARE
 LISTED IN ACCORDANCE WITH UL 1995- SEE SECTION 908.1.
  
 2) SHEET M1: PROVIDE THE TONNAGE OF THE TOWERS IN THE
 EQUIPMENT SCHEDULE.
  
 3) PER MANUFACTURER'S SPECIFICATIONS: INDICATE THE
 REQUIRED CLEARANCES AROUND THE TOWERS FOR SERVICE, AND
 THE REQUIRED CLEARANCE FOR THE AIR INTAKE TO THE
 ADJACENT UPPER ROOF WALL.
  
 4) PROVIDE A PERMANENT LADDER AND PLATFORM TO ACESS THE
 PLENUM AND THE MOTOR- SECTION 306.5
  
 5) THE $135,000 VALUE ON THE PERMIT APPLICATION APPEARS
 TOO LOW FOR THE SCOPE OF WORK. PLEASE SEE SECTION 109.3
 WPB AMENDMENTS TO THE FBC AND PROVIDE A CONTRACT OR BID
 DOCUMENT TO VERIFY COSTS THAT INCLUDE: A) LABOR,
 MATERIALS AND EQUIPMENT FOR MECHANICAL, ELECTRICAL, AND
 PLUMBING WORK. B) DEMOLITION, SITE WORK AND CRANE, AND
 DESIGN FEES.
  
 6) PROVIDE A COMMISSIONING PLAN IN ACCORDANCE WITH
 SECTIONS C408.2 & C408.2.1 FBC-14 ENERGY CONSERVATION.
  