Plan Review Notes For Permit 17070528 |
Permit Number |
17070528 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-07-18 10:08:57 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #17070528 | | 7/18/17 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PROVIDE VERIFICATION THAT THE COOLING TOWERS ARE | | LISTED IN ACCORDANCE WITH UL 1995- SEE SECTION 908.1. | | | | 2) SHEET M1: PROVIDE THE TONNAGE OF THE TOWERS IN THE | | EQUIPMENT SCHEDULE. | | | | 3) PER MANUFACTURER'S SPECIFICATIONS: INDICATE THE | | REQUIRED CLEARANCES AROUND THE TOWERS FOR SERVICE, AND | | THE REQUIRED CLEARANCE FOR THE AIR INTAKE TO THE | | ADJACENT UPPER ROOF WALL. | | | | 4) PROVIDE A PERMANENT LADDER AND PLATFORM TO ACESS THE | | PLENUM AND THE MOTOR- SECTION 306.5 | | | | 5) THE $135,000 VALUE ON THE PERMIT APPLICATION APPEARS | | TOO LOW FOR THE SCOPE OF WORK. PLEASE SEE SECTION 109.3 | | WPB AMENDMENTS TO THE FBC AND PROVIDE A CONTRACT OR BID | | DOCUMENT TO VERIFY COSTS THAT INCLUDE: A) LABOR, | | MATERIALS AND EQUIPMENT FOR MECHANICAL, ELECTRICAL, AND | | PLUMBING WORK. B) DEMOLITION, SITE WORK AND CRANE, AND | | DESIGN FEES. | | | | 6) PROVIDE A COMMISSIONING PLAN IN ACCORDANCE WITH | | SECTIONS C408.2 & C408.2.1 FBC-14 ENERGY CONSERVATION. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|