Plan Review Notes For Permit 17070496 |
Permit Number |
17070496 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2017-09-05 18:15:26 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE GENERAL NOTE 2 ON THE GENERATOR PAD ENGINEERING | | REQUIRES THAT THE CALCULATIONS FOR POSITIVE AND | | NEGATIVE DESIGN PRESSURES FOR USE WITH THIS SYSTEM BE | | DETERMINED BY OTHERS ON A JOB SPECIFIC BASIS IN | | ACCORDANCE WITH THE GOVERING CODE. THIS SYSTEM IS | | LOCATED IN EXPOSURE C AND 170 MPH VULT WINDSPEED. | | SUBMIT THE REQUIRED DESIGN PRESSURES FOR THIS SYSTEM. | | FBC 301.2.1 NOTE THAT THE ALLOWABLE PRESSURE IS 39.20 | | PSF FOR THE 22KW GENERATOR. |
|