Plan Review Notes
Plan Review Notes For Permit 17070496
Permit Number 17070496
Review Stop B
Sequence Number 2
Notes
Date Text
2017-09-05 18:15:26PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERAL NOTE 2 ON THE GENERATOR PAD ENGINEERING
 REQUIRES THAT THE CALCULATIONS FOR POSITIVE AND
 NEGATIVE DESIGN PRESSURES FOR USE WITH THIS SYSTEM BE
 DETERMINED BY OTHERS ON A JOB SPECIFIC BASIS IN
 ACCORDANCE WITH THE GOVERING CODE. THIS SYSTEM IS
 LOCATED IN EXPOSURE C AND 170 MPH VULT WINDSPEED.
 SUBMIT THE REQUIRED DESIGN PRESSURES FOR THIS SYSTEM.
 FBC 301.2.1 NOTE THAT THE ALLOWABLE PRESSURE IS 39.20
 PSF FOR THE 22KW GENERATOR.