2017-07-25 13:31:51 | CODES IN EFFECT: |
| FLORIDA BUILDING CODE 2014 5TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| EDITION |
| NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND |
| SEALED BY A DESIGN PROFESSIONAL OR THE ELECTRICAL |
| CONTRACTOR QUALIFIER. FS 471.003(2)(H); 471.025; FBC |
| 107.2.1, 107.3.5 |
| 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, |
| AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY |
| WITH CODE. NEC 210.8, 210.12, 215.5, 408.4 |
| 3. LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE |
| SUITABLE FOR DAMP LOCATIONS. PLEASE SPECIFY ON PLAN. |
| NEC 410.10(D), 110.3 |
| 4. LIGHTING WITH OPEN OR PARTIALLY ENCLOSED LAMPS AND |
| PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT BE |
| PERMITTED IN CLOTHES CLOSETS. SPECIFY TYPE OF FIXTURE |
| ON PLAN. NEC 410.16(B), 110.3 |
| 5. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A |
| NOTE WILL SUFFICE. NEC 406.12 |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |