2017-07-18 12:19:32 | 2014 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 17070488 |
| ADD: 400 N. FLAGLER DR. SUITE: 2202 |
| CONT: PHILLIP E. JOHNSON, INC. |
| TEL: 561-366-1034 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: TUES. JULY 18/2017 |
| ACTION: DENIED |
| |
| 1) 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION 107.3.4.3 CERTIFICATION BY CONTRACTOR. |
| PLEASE NOTE THE EXCEPTION TO ENGINEERED PLANS UNDER |
| 471.003(H) ELECTRICAL/ PLUMBING/ MECHANICAL, |
| 481.229(1)(C) (BUILDING) REQUIRES THE CONTRACTOR FOR |
| THAT TRADE THAT WILL BE LICENSED IN THAT TRADE, WILL |
| ALSO BE THE CONTRACTOR THAT DESIGNS THE SYSTEM UNDER |
| THAT TRADE. FOR EACH TRADE THE CONTRACTOR RESPONSIBLE |
| FOR THE DESIGN UNDER THE TRADE LICENSED IN MUST PRINT |
| THEIR NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE |
| THESE PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY |
| WOULD HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND |
| PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER |
| ONE SHEET. |
| 2) THE PERMIT APPLICATION IN THE MASTER BATH AND GUEST |
| BATH NEW TILE FLOORS ARE WITHIN THE SCOPE OF THIS |
| PERMIT. |
| BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B |
| 2014) FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING |
| ALL NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED |
| FLOOR ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET |
| THE QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS |
| FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED |
| CEILING. PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE |
| WITH: |
| 2A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| |
| 2B) FBC-B 2014 1207.2 AIR-BORNE SOUND. WALLS, |
| PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING |
| DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR |
| AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E |
| 90. |
| |
| 2C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2. |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| |
| 3) THE PERMIT APPLICATION IN THE MASTER BATH AND GUEST |
| BATH NEW TILE WALLS. PLEASE PROVIDE WHAT TYPE OF WALL |
| BOARD, (BACKER BOARD FOR TILE), HOW COMPLIANCE WITH |
| SECTION 2509.2 BASE FOR TILE. |
| |
| SEE 2014 FBC-B 2509.2 BASE FOR TILE. GLASS MAT |
| WATER-RESISTANT GYPSUM BACKING PANELS, DISCRETE |
| NONASBESTOS FIBER-CEMENT INTERIOR SUBSTRATE SHEETS OR |
| NONASBESTOS FIBER-MAT REINFORCED CEMENTITIOUS BACKER |
| UNITS IN COMPLIANCE WITH ASTM C 1178, C 1288 OR C 1325 |
| AND INSTALLED IN ACCORDANCE WITH MANUFACTURER |
| RECOMMENDATIONS SHALL BE USED AS A BASE FOR WALL TILE |
| IN TUB AND SHOWER AREAS AND WALL AND CEILING PANELS IN |
| SHOWER AREAS. WATER-RESISTANT GYPSUM BACKING BOARD |
| SHALL BE USED AS A BASE FOR TILE IN WATER CLOSET |
| COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE WITH |
| GA-216 OR ASTM C 840 AND MANUFACTURER RECOMMENDATIONS. |
| REGULAR GYPSUM WALLBOARD IS PERMITTED UNDER TILE OR |
| WALL PANELS IN OTHER WALL AND CEILING AREAS WHEN |
| INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C 840. |
| |
| 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| JAMES A. WITMER BN, PX, CBO |