Plan Review Notes For Permit 17070475 |
Permit Number |
17070475 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-08-09 11:12:55 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #17070475 | | 8/9/17 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHOW WHERE THE AIR HANDLER WAS PREVIOUSLY LOCATED, | | AND ALL REQUIRED ALTERATIONS TO THE DUCTWORK TO | | ACCOMODATE THE NEW LOCATION. | | | | 2) PROVIDE AN ELECTRICAL PLAN, AND AN ELECTRICAL | | SUB-PERMIT. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|