Plan Review Notes For Permit 17070443 |
Permit Number |
17070443 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2017-08-01 12:33:13 | 1) SUBMIT 2 SETS OF PROFESSIONALLY DRAWN PLANS THAT | | CLEARLY REFLECTS THE ENTIRE SCOPE OF WORK TO BE DONE | | INCLUDING ANY BUILDING, ELECTRICAL OR MECHANICAL WORK. | | WPB AMEND. TO FBC SECS. 107.1, 107.2.1. 2ND REQUEST | | 2) SHOW THE PROPOSED TYPE OF OCCUPANCY ON THE PLANS PER | | THE FBC SEC.302.1. 2ND REQUEST. | | 3) INDICATE THE OCCUPANT LOAD OF THIS SPACE PER THE FBC | | SEC.1004.1.2.2ND REQUEST. | | 4) IS THIS A CHANGE OF OCCUPANCY PER THE FBC- EXISTING | | BUILDING CODE SEC.1001.3. INDICATE THE PREVIOUS | | OCCUPANCY OF THE SPACE ON THE PLANS. THE SUBMITTED | | PLANS MARKED "FOR REFERENCE ONLY" DO NOT CONTAIN THIS | | REQUIRED INFORMATION. 2ND REQUEST. | | 5) SUBMIT A WATER RISER DIAGRAM FOR THE NEW PLUMBING | | WORK. WPB AMEND. TO FBC SEC. 107.3.5.1.3. 2ND REQUEST. | | | | I SUGGEST SETTING UP A MEETING WITH ME TO DISCUSS THE | | PLAN REVIEW COMMENTS ONCE THE REVIEW IS COMPLETE. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | |
|