Plan Review Notes
Plan Review Notes For Permit 17070443
Permit Number 17070443
Review Stop P
Sequence Number 1
Notes
Date Text
2017-07-24 10:25:371) SUBMIT 2 SETS OF PROFESSIONALLY DRAWN PLANS THAT
 CLEARLY REFLECTS THE ENTIRE SCOPE OF WORK TO BE DONE
 INCLUDING ANY BUILDING, ELECTRICAL OR MECHANICAL WORK.
 WPB AMEND. TO FBC SECS. 107.1, 107.2.1.
 2) SHOW THE PROPOSED TYPE OF OCCUPANCY ON THE PLANS PER
 THE FBC SEC.302.1.
 3) INDICATE THE OCCUPANT LOAD OF THIS SPACE PER THE FBC
 SEC.1004.1.2.
 4) IS THIS A CHANGE OF OCCUPANCY PER THE FBC- EXISTING
 BUILDING CODE SEC.1001.3.? INDICATE THE PREVIOUS
 OCCUPANCY OF THE SPACE ON THE PLANS.
 5) SUBMIT A SANITARY AND WATER RISER DIAGRAM FOR THE
 NEW PLUMBING WORK. WPB AMEND. TO FBC SEC. 107.3.5.1.3.
 A VENT IS REQUIRED ON THE SUMP PER FBC 712.3.2.
 6) THE WATER HEATER RELIEF LINE SHALL DISCHARGE THROUGH
 AN AIR GAP LOCATED IN THE SAME ROOM AS THE WATER
 HEATER. FBC-PLUMBING SEC.504.6.
 7) SUBMIT A FLOOR PLAN SHOWING THE LOCATION OF THE
 EXISTING ACCESSIBLE TOILET ROOM AS NOTED ON THE
 APPLICATION.WPB AMEND. TO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW