Plan Review Notes
Plan Review Notes For Permit 17070394
Permit Number 17070394
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-07-13 17:11:43PERMIT #17070394
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1) ALL PROPANE TANKS MUST BE DISCONNECTED FROM VEHICLES
 AND PROPERLY CAPPED TO AVOID ACCIDENTAL USE.
 2) RV SHOW STAFF MEMBERS ARE TO VISUALLY INSPECT EACH
 VEHICLE BEFORE, DURING, AND AFTER EACH SHOW DAY TO
 ENSURE THAT PROPANE TANKS REMAIN DISCONNECTED AND THAT
 THERE ARE NO VISIBLE FUEL LEAKS.
 3) ALL DRIVE LANES ARE TO REMAIN FREE OF OBSTRUCTIONS
 AND ACCESSIBLE TO EMERGENCY VEHICLES, DURING THE FULL
 LENGTH OF THE SHOW.
 4) RVS MAY ONLY BE PARKED IN THE AREAS MARKED FOR
 PARKED VEHICLES (I.E. WITHIN THE STRIPED LINES, NOT IN
 THE DRIVE AREAS.)
 5) A WALK THROUGH BY A FIRE INSPECTOR MAY AND WILL BE
 CONDUCTED AT ANY POINT DURING THE DURATION OF THIS
 EVENT.
  
 SUE ELLEN CALDERON
 ASST. FIRE MARSHAL
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  