2017-07-27 15:15:59 | CODES IN EFFECT: |
| FLORIDA BUILDING CODE 2014 5TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| EDITION |
| NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. NOTE 2 ON PANEL SCHEDULE STATES RECEPTACLES SHALL BE |
| "TEMPER RESISTANT PER 210.12". THERE IS SIMILAR WORDING |
| IN NOTE 4, BUT THIS NOTE STATES "PER 406.11".IF YOU ARE |
| REFERRING TO TAMPER RESISTANT REQUIREMENTS, NEITHER OF |
| THESE CODE SECTIONS APPLY. PROVIDE CLARIFICATION AND/OR |
| CORRECTION. NEC 406.12; FBC RE4002.14, FBC 107.2.1 |
| 2. NOTE 3 STATES THAT "ALL NEW BRANCH CIRCUITS SHALL BE |
| AFCI PROTECTED PER 210.12". NEC 210.12 DOES NOT REQUIRE |
| ALL CIRCUITS TO BE AFCI PROTECTED, BUT THE STATEMENT |
| DOES. IS THIS THE INTENTION, OR WILL ONLY THE CIRCUITS |
| REQUIRED PER NEC 210.12 BE AFCI PROTECTED? PLEASE |
| CLARIFY AND/OR CORRECT. NEC 210.12; FBC RE3902.12 |
| 3. PROVIDE GFCI PROTECTED OUTLET IN SHED. NEC |
| 210.52(G)(1), 210.8; FBC RE3901.9, RE3902.2 |
| 4. LIGHT IN SHED NEED TO BE CONTROLLED BY A SWITCH. NEC |
| 210.70(2)(A); FBC RE3903.3 |
| 5. SHED NEEDS TO HAVE EXTERIOR LIGHT AT ENTRY/EXIT |
| CONTROLLED BY SWITCH. NEC 210.70(2)(B); FBC RE3903.3 |
| 6. CIRCUIT 25 SHOWS A #14 WIRE ON A 20 AMP BREAKER. |
| PROVIDE CORRECTION. NEC 240.4, 310.15(B)(16); FBC |
| RE3702.13 |
| 7. CIRCUIT 2,4 SHOWS A #12 WIRE ON A 50 AMP BREAKER. |
| PROVIDE CORRECTION. NEC 240.4, 310.15(B)(16); FBC |
| RE3702.13 |
| 8. CIRCUIT 10,12 SHOWS A #12 WIRE ON A 30 AMP BREAKER |
| FOR WATER HEATER. PROVIDE CORRECTION. 4500 WATT WATER |
| HEATER SPECIFIED ON PLUMBING PLAN SHOULD HAVE A 25 AMP |
| BREAKER. PROVIDE CORRECTION. NEC 240.4, 310.15(B)(16), |
| 422.13; FBC RE3702.13 |
| 9. AHU AND CU SPECS SHOW DIFFERENT SIZE CIRCUIT |
| REQUIREMENTS THAN SHOWN ON PANEL SCHEDULE. PROVIDE |
| CORRECTION. NEC 110.3, 215.5; FBC 107.2.1 |
| 10. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL |
| LOADS. NEC 220; FBC RE3602.3 |
| 11. DINING ROOM SHOWS A 15 AMP CIRCUIT. PROVIDE |
| CORRECTION. NEC 210.52(B)(1); FBC RE3703.2 |
| 12. COUNTER TOP RECEPTACLES IN THE KITCHEN REQUIRE A |
| MINIMUM OF TWO 20 AMP CIRCUITS. PROVIDE CORRECTION. NEC |
| 210.52(B)(1); FBC RE3703.2 |
| 13. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C |
| EQUIPMENT PER CODE. NEC 210.63; FBC RE3901.12 |
| 14. PLAN DOES NOT SHOW THE 20 AMP RECEPTACLE IN THE |
| LAUNDRY REQUIRED PER CODE. PROVIDE CORRECTION. NEC |
| 210.52(F); FBC RE3901.8 |
| 15. WALL OUTLET IN LAUNDRY IS ON SAME CIRCUIT WITH THE |
| BATH GFCI OUTLETS. PROVIDE CORRECTION. NEC 210.11(C)(3) |
| , FBC RE3703.4 |
| 16. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| FBC EC R404.1 |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |