Plan Review Notes
Plan Review Notes For Permit 17070366
Permit Number 17070366
Review Stop E
Sequence Number 1
Notes
Date Text
2017-07-27 15:15:59CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NOTE 2 ON PANEL SCHEDULE STATES RECEPTACLES SHALL BE
 "TEMPER RESISTANT PER 210.12". THERE IS SIMILAR WORDING
 IN NOTE 4, BUT THIS NOTE STATES "PER 406.11".IF YOU ARE
 REFERRING TO TAMPER RESISTANT REQUIREMENTS, NEITHER OF
 THESE CODE SECTIONS APPLY. PROVIDE CLARIFICATION AND/OR
 CORRECTION. NEC 406.12; FBC RE4002.14, FBC 107.2.1
 2. NOTE 3 STATES THAT "ALL NEW BRANCH CIRCUITS SHALL BE
 AFCI PROTECTED PER 210.12". NEC 210.12 DOES NOT REQUIRE
 ALL CIRCUITS TO BE AFCI PROTECTED, BUT THE STATEMENT
 DOES. IS THIS THE INTENTION, OR WILL ONLY THE CIRCUITS
 REQUIRED PER NEC 210.12 BE AFCI PROTECTED? PLEASE
 CLARIFY AND/OR CORRECT. NEC 210.12; FBC RE3902.12
 3. PROVIDE GFCI PROTECTED OUTLET IN SHED. NEC
 210.52(G)(1), 210.8; FBC RE3901.9, RE3902.2
 4. LIGHT IN SHED NEED TO BE CONTROLLED BY A SWITCH. NEC
 210.70(2)(A); FBC RE3903.3
 5. SHED NEEDS TO HAVE EXTERIOR LIGHT AT ENTRY/EXIT
 CONTROLLED BY SWITCH. NEC 210.70(2)(B); FBC RE3903.3
 6. CIRCUIT 25 SHOWS A #14 WIRE ON A 20 AMP BREAKER.
 PROVIDE CORRECTION. NEC 240.4, 310.15(B)(16); FBC
 RE3702.13
 7. CIRCUIT 2,4 SHOWS A #12 WIRE ON A 50 AMP BREAKER.
 PROVIDE CORRECTION. NEC 240.4, 310.15(B)(16); FBC
 RE3702.13
 8. CIRCUIT 10,12 SHOWS A #12 WIRE ON A 30 AMP BREAKER
 FOR WATER HEATER. PROVIDE CORRECTION. 4500 WATT WATER
 HEATER SPECIFIED ON PLUMBING PLAN SHOULD HAVE A 25 AMP
 BREAKER. PROVIDE CORRECTION. NEC 240.4, 310.15(B)(16),
 422.13; FBC RE3702.13
 9. AHU AND CU SPECS SHOW DIFFERENT SIZE CIRCUIT
 REQUIREMENTS THAN SHOWN ON PANEL SCHEDULE. PROVIDE
 CORRECTION. NEC 110.3, 215.5; FBC 107.2.1
 10. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. NEC 220; FBC RE3602.3
 11. DINING ROOM SHOWS A 15 AMP CIRCUIT. PROVIDE
 CORRECTION. NEC 210.52(B)(1); FBC RE3703.2
 12. COUNTER TOP RECEPTACLES IN THE KITCHEN REQUIRE A
 MINIMUM OF TWO 20 AMP CIRCUITS. PROVIDE CORRECTION. NEC
 210.52(B)(1); FBC RE3703.2
 13. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C
 EQUIPMENT PER CODE. NEC 210.63; FBC RE3901.12
 14. PLAN DOES NOT SHOW THE 20 AMP RECEPTACLE IN THE
 LAUNDRY REQUIRED PER CODE. PROVIDE CORRECTION. NEC
 210.52(F); FBC RE3901.8
 15. WALL OUTLET IN LAUNDRY IS ON SAME CIRCUIT WITH THE
 BATH GFCI OUTLETS. PROVIDE CORRECTION. NEC 210.11(C)(3)
 , FBC RE3703.4
 16. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  