Plan Review Notes
Plan Review Notes For Permit 17070363
Permit Number 17070363
Review Stop M
Sequence Number 1
Notes
Date Text
2017-07-21 14:36:211ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17070363
 7/21/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) M2.1: THE CORRIDOR SHALL NOT BE USED TO RETURN AIR
 TO THE AHU- SECTION 601.2
  
 2) M2.1: PROVIDE THE FLEX DUCT SIZES.
  
 3) M2.1: VERIFY THE REQUIRED CLEARANCES FOR THE O/A
 INTAKE AND PROVIDE OPENING PROTECTIONS- SEE SECTIONS
 401.4 AND 401.5
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  