Plan Review Notes For Permit 17070363 |
Permit Number |
17070363 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-07-21 14:36:21 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #17070363 | | 7/21/17 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) M2.1: THE CORRIDOR SHALL NOT BE USED TO RETURN AIR | | TO THE AHU- SECTION 601.2 | | | | 2) M2.1: PROVIDE THE FLEX DUCT SIZES. | | | | 3) M2.1: VERIFY THE REQUIRED CLEARANCES FOR THE O/A | | INTAKE AND PROVIDE OPENING PROTECTIONS- SEE SECTIONS | | 401.4 AND 401.5 | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|