2017-07-17 08:31:05 | 2014 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 17070363 |
| ADD: 477 S. ROSEMARY AVE., SUITE: 228 |
| CONT: TBD/ TO BE DETERMINED |
| TEL: 561-856-6655 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: MON. JULY 17, 2017 |
| ACTION: DENIED |
| |
| 1) SHEET LS1.0 & A1.01 BUSINESS OCCUPANCY/ NOT A CHANGE |
| IN OCCUPANCY LAST PERMIT ACTIVITY PERMIT: 12020020: |
| 1A) BOTH SHEETS SHOW THE FRONT ENTRY, ON THE INTERIOR |
| LATCH SIDE, THE PLANS DO NOT INDICATE COMPLIANCE WITH |
| MANEUVERING CLEARANCES, REQUIRED 18 INCHES LATCH SIDE |
| OF THE DOOR. 2014 FBC-ACCESSIBILITY CODE SECTION |
| ACCESS. CODE 404.2.4 MANEUVERING CLEARANCES. / FIGURE |
| 404.2.4.1(A). MINIMUM MANEUVERING CLEARANCES AT DOORS |
| AND GATES SHALL COMPLY WITH 404.2.4. MANEUVERING |
| CLEARANCES SHALL EXTEND THE FULL WIDTH OF THE DOORWAY |
| AND THE REQUIRED LATCH SIDE OR HINGE SIDE CLEARANCE. |
| PERMIT 12020020 WAS FOR A CHANGE OF OCCUPANCY |
| RESIDENTIAL TO BUSINESS. THE PLANS WERE REDLINED/ |
| PROVISO FOR AN ACCESSIBLE FRONT DOOR UNDER THE |
| 2007/02009 FBC- B 11-4.13.6 MANEUVERING CLEARANCES AT |
| DOORS. |
| |
| 1B) SHEET LS1.0, A1.01 & A2.0 ALL OF THE FLOOR PLAN, |
| SHEET A2.0 IS DETAILED SECTIONS OF THE FLOOR PLAN |
| DETAIL (A) IS AN ENLARGE DETAIL OF THE ACCESSIBLE |
| RESTROOM, THE RESTROOM DOES NOT HAVE ANY DIMENSIONS AS |
| TO THE SIZE OF THE RESTROOM, FIXTURES DISTANCE FROM |
| WALLS TO THE NEXT FIXTURE, BACKING FOR FIXTURES AND |
| COMPLIANCE WITH THE 2014 FBC-ACCESSIBILITY CODE |
| SECTION: |
| |
| 604.2 LOCATION. THE WATER CLOSET SHALL BE POSITIONED |
| WITH A WALL OR PARTITION TO THE REAR AND TO ONE SIDE. |
| THE CENTERLINE OF THE WATER CLOSET SHALL BE 16 INCHES |
| (405 MM) MINIMUM TO 18 INCHES (455 MM) MAXIMUM FROM THE |
| SIDE WALL OR PARTITION, EXCEPT THAT THE WATER CLOSET |
| SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES (485 |
| MM) MAXIMUM FROM THE SIDE WALL OR PARTITION IN THE |
| AMBULATORY ACCESSIBLE TOILET COMPARTMENT SPECIFIED IN |
| 604.8.2. WATER CLOSETS SHALL BE ARRANGED FOR A |
| LEFT-HAND OR RIGHT-HAND APPROACH. |
| |
| 1C) SHEET LS1.0, A1.01 & A2.0 ALL OF THE FLOOR PLAN, |
| SHEET A2.0 IS DETAILED SECTIONS OF THE FLOOR PLAN |
| DETAIL (A) IS AN ENLARGE DETAIL OF THE ACCESSIBLE |
| RESTROOM, 604.3.1 SIZE 604.3.2 OVERLAP. THE REQUIRED |
| CLEARANCE AROUND THE WATER CLOSET SHALL BE PERMITTED TO |
| OVERLAP THE WATER CLOSET, ASSOCIATED GRAB BARS, |
| DISPENSERS, SANITARY NAPKIN DISPOSAL UNITS, COAT HOOKS, |
| SHELVES, ACCESSIBLE ROUTES, CLEAR FLOOR SPACE AND |
| CLEARANCES REQUIRED AT OTHER FIXTURES, AND THE TURNING |
| SPACE. NO OTHER FIXTURES OR OBSTRUCTIONS SHALL BE |
| LOCATED WITHIN THE REQUIRED WATER CLOSET CLEARANCE. |
| |
| 1D) SHEET LS1.0, A1.01 & A2.0 ALL OF THE FLOOR PLAN, |
| SHEET A2.0 IS DETAILED SECTIONS OF THE FLOOR PLAN |
| DETAIL (A) IS AN ENLARGE DETAIL OF THE ACCESSIBLE |
| RESTROOM. THIS SAME SHEET (A2.0) DETAIL C SHOWS THE |
| REAR ELEVATION OF THE RESTROOM, MISSING CENTER LINE OF |
| WATER CLOSET TO THE NEAREST SIDE WALL AND THE DISTANCE |
| OF THE REAR GRAB BAR IN COMPLIANCE WITH 604.5.2 REAR |
| WALL. THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 |
| MM) LONG MINIMUM AND EXTEND FROM THE CENTERLINE OF THE |
| WATER CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND |
| 24 INCHES (610 MM) MINIMUM ON THE OTHER SIDE. |
| |
| 1E) SHEET LS1.0 & A1.01 BOTH SHOW CLOSET DOORS 229 & |
| 236 BOTH ARE LESS THAN A 36 WIDE DOOR. PLEASE SHOW |
| COMPLIANCE WITH THE 2014 FBC-ACCESSIBILITY CODE SECTION |
| 404.2.3 CLEAR WIDTH. OPENINGS MORE THAN 24 INCHES (610 |
| MM) DEEP SHALL PROVIDE A CLEAR OPENING OF 36 INCHES |
| (915 MM) MINIMUM. |
| 404.2.4 MANEUVERING CLEARANCES. 404.2.4.1 SWINGING |
| DOORS AND GATES. SWINGING DOORS AND GATES SHALL HAVE |
| MANEUVERING CLEARANCES COMPLYING WITH TABLE 404.2.4.1 |
| |
| 2) PLEASE PROVIDE A LETTER INDICATING COMPLIANCE WITH |
| THE 2014 ACCESSIBILITY CODE 202.4.2 ACCESSIBLE FEATURES |
| IN THE EVENT OF DISPROPORTIONALITY. THE VALUE OF THIS |
| PERMIT WOULD REQUIRE A VALUE OF $19,600 DOLLARS IN |
| UPGRADES TO MEET DISPROPORTIONALITY. |
| 2014 ACCESSIBILITY CODE 202.4.2 ACCESSIBLE FEATURES IN |
| THE EVENT OF DISPROPORTIONALITY. |
| WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH |
| OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS |
| DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION, |
| THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE |
| EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING |
| DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE |
| ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE |
| ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE |
| FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN |
| ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST |
| ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX |
| RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE |
| DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL |
| ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND |
| ALARMS. |
| |
| 3) SHEET A1.0.1. INDICATES (3) WINDOWS NEXT TO THE |
| LATCH SIDE OF SWING DOORS. THE WINDOW SCHEDULE ALSO ON |
| THE SAME PAGE IN THE NOTE SECTION THERE IS NO MENTION |
| OF SAFETY GLAZING REQUIREMENT 2406.4.2 OF THE 2014 |
| FBC-B. GLAZING ADJACENT TO DOORS. GLAZING IN AN |
| INDIVIDUAL FIXED OR OPERABLE PANEL ADJACENT TO A DOOR |
| WHERE THE NEAREST VERTICAL EDGE OF THE GLAZING IS |
| WITHIN A 24-INCH (610 MM) ARC OF EITHER VERTICAL EDGE |
| OF THE DOOR IN A CLOSED POSITION AND WHERE THE BOTTOM |
| EXPOSED EDGE OF THE GLAZING IS LESS THAN 60 INCHES |
| (1524 MM) ABOVE THE WALKING SURFACE SHALL BE CONSIDERED |
| A HAZARDOUS LOCATION. |
| NOTE: SHEET A3.0 DETAIL # 7 SHOWS A TEMPERED GLASS |
| DETAIL BUT THERE IS NO CUT SECTIONS ON SHEET A1.01 |
| REFERENCING THIS DETAIL, 107.2.1.3 ADDITIONAL |
| INFORMATION IS REQUIRED. |
| |
| 4) SHEET A2.0 DETAIL A THE BREAK ROOM ON THE RIGHT SIDE |
| OF THE DETAIL THERE APPEARS TO BE CABINETS AND POSSIBLY |
| A STOVE, THEY SHOW ON THE DEMOLITION SHEET, WHY ARE |
| THESE LINES THERE, IF THEY ARE DEMO LINES THEY SHOULD |
| BE TURNED OFF, SINCE THIS SHEET REPRESENTS NEW WORK. |
| THE LINES REPRESENTED ARE NOT DEMO LINES, THEN WHAT DO |
| THEY REPRESENT? 107.2.1.3 ADDITIONAL INFORMATION IS |
| REQUIRED. |
| |
| 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| JAMES A. WITMER BN, PX, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |