Plan Review Notes
Plan Review Notes For Permit 17070341
Permit Number 17070341
Review Stop B
Sequence Number 1
Notes
Date Text
2017-09-13 15:52:361ST REVIEW: FBC 2014 5TH ED
 CITY CODE SECTION 78-490
  
 NOT APPROVED, SEE BELOW:
  
 1) ALTHOUGH YOU PROVIDED A PARKLET PERMIT APPLICATION,
 PLEASE ADDITIONALLY PROVIDE A BUILDING PERMIT
 APPLICATION FORM WITH CONTRACTOR AND OWNER INFORMATION
 AND SIGNATURES. LIST THE CITY OF WEST PALM BEACH IN BOX
 9 ON THE REAR OF THE APPLICATION.
  
 2) PROVIDE TWO SETS OF PLANS, ONLY ONE WAS FOUND. PLANS
 SHALL BE SIGNED AND SEALED BY THE DESIGNER OF RECORD
 PURSUANT TO FLORIDA ADMINISTRATIVE CODE RULE 61G1.
  
 3) CITY CODE 78-497 (B)()C. - WIND RESISTANCE - SPECIFY
 THE WIND RESISTANCE STANDARD UTILIZED IN THE DESIGN OF
 THE PARKLET. PROVIDE DETAILS FOR FASTENING SUCH AS NAIL
 TYPE & SPACING, CONNECTORS AND CONNECTION TO EARTH. IT
 APPEARS THERE IS NOT INTENT TO DESIGN FOR WIND
 RESISTANCE PURSUANT TO FBC CHAPTER 16 FOR THE LOCATION
 AS RISK CATEGORY II BUT REATHER FOR A LESSER WIND
 RESISTANCE WITH INTEND TO REMOVE IN THE EVENT OF
 FORCASTED HIGH WINDS. IF THE LATER, PROVIDE DETAILS FOR
 THE MAXIMUM WIND DESIGN. FOR EXAMPLE, IF THE INTENT IS
 TO REMOVE PRIOR TO FORECASTED 75 MPH WINDS, PROVIDE A
 DESIGN CAPABLE OF WITHSTANDING 90 MPH WINDS AND PROVIDE
 THE REMOVAL PLAN.
  
 4) CITY CODE 78-497 (B)(1)F. - ACCESSIBILITY - PLEASE
 INDICATE THE INTENT TO COMPLY WITH FBC ACCESSIBILITY
 CHAPTER 3 AS TO APPROACH, GROUND SURFACES, OPENINGS IN
 FLOOR SURFACES, CHANGES IN LEVEL, AND TURNING SPACE,
 MANEUVERING, AND CLEARANCES AND TABLE TOP HEIGHTS PER
 CHAPTER 3. ADDITIONALLY, PROVIDE A SEATING PLAN TO SHOW
 COMPLIANCE WITH FBC ACCESSIBILITY TABLE 221.2.1.1
  