Plan Review Notes
Plan Review Notes For Permit 17070327
Permit Number 17070327
Review Stop B
Sequence Number 2
Notes
Date Text
2017-08-25 16:32:352014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17070327
 ADD: 1885 OKEECHOBEE BLVD. / SUITE 1885
 CONT: DUKE INDIANA CONSTRUCTION
 TEL: 954-453-5261
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRI. AUGUST 25/ 2017
 ACTION: DENIED
  
 1) COMPLIED.
  
 2) THERE IS ADDITIONAL INFORMATION REQUIRED BY BOTH
 BUILDING AND FIRE. THE OCCUPANCY IS DECLARED TO BE A S1
 OCCUPANCY, BUT THE TYPE OF BUSINESS, STORAGE OF
 COMBUSTIBLES HAS NOT BEEN DECLARED. WITH THE STORAGE OF
 MATTRESSES, (EXAMPLES) FURNITURE OR TIRES WITHIN THE
 RACK STORAGE, ADDITIONAL SPRINKLER HEADS MAYBE REQUIRED
 WITHIN THE RACKS THEMSELVES. THE EXISTING FIRE
 SPRINKLER SYSTEM MAYBE UNDER SIZED FOR THE AMOUNT OF
 COMBUSTIBLE FIRE LOADS.
  
 1ST ROUND OF COMMENTS. THE LIFE SAFETY PLAN SHEET A203
 SHOWS THERE IS TO BE RACK STORAGE BUT THE PLANS DO NOT
 PROVIDE HOW HIGH THE RACK STORAGE WILL BE? THE 2014
 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS
 TO THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 SECTION 105.2 (6) REQUIRES A PERMIT FOR RACK STORAGE
 WHEN THE RACKS ARE FIXED IN PLACE AND THE RACKS ARE
 OVER 5 FOOT 9 INCHES IN HEIGHT.
  
 3) A SEPARATE PERMIT WILL BE REQUIRED FOR THE RACK
 STORAGE BUT UNTIL THE TYPES OF RACKS, HEIGHT OF RACKS,
 IF THE RACKS HAS AERIAL WALKWAYS, FLOOR OF GRID WORK
 STEEL, STAIRS, AND THE TYPE OF COMBUSTIBLE IN THE
 RACKS, TO MANY UNKNOWNS TO ISSUE A PERMIT FOR THE S1
 OCCUPANCY. FBC-B 903.2.9.
  
 1ST ROUND OF COMMENTS. THE LIFE SAFETY PLAN SHEET A203
 ALSO INDICATES MOST OF THE WAREHOUSE TO BE PALLET
 STORAGE. THE PLANS DO NOT INDICATE HOW HIGH THE PALLETS
 ARE TO BE STORED. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT