2017-08-14 14:55:55 | 1ST REVIEW: FBC 2014 5TH EDITION |
| |
| PLUMBING COMMENTS: |
| |
| 1. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL |
| POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE |
| THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING |
| SURFACE. |
| |
| 2. THE GRAB BAR ON TH E REAR WALL SHALL COMPLY WITH FBC |
| ACC 604.5.2 REAR WALL. |
| THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG |
| MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER |
| CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24 |
| INCHES (610 MM) MINIMUM ON THE OTHER SIDE. |
| |
| 3. TOILET DISPENSER SHALL COMPLY WITH FBC ACC 604.7 |
| DISPENSERS. |
| TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230 |
| MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO |
| THE CENTERLINE OF THE DISPENSER |
| |
| 4. THE BRANCH DRAIN FOR THE NEW MOP SINK AND BREAK ROOM |
| SINK SHALL CONNECT TO BUILDING DRAIN DOWN STREAM OF THE |
| BATHROOM GROUP. PER FBC PL 912.1 |
| |
| 5. A BACK FLOW IS REQUIRED ON THE REFRIGERATOR ICE |
| MACHINE. PER FBC PL 608.3 |
| |
| 6. SHT. P3.1 THE WATER HEATER STAND AND PLATFORM |
| DETAILS DON,T MATCH PLEASE CLARIFY. PER WPB AMEND TO |
| FBC 107.2.1 |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |