Date |
Text |
2017-07-17 15:50:02 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| |
| 1) SHEET A203 - THERE ARE TWO DOUBLE DOORS LEADING FROM |
| THE WAREHOUSE TO THE OFFICE AREA. THERE DOES ARE |
| INDICATING AS SWINGING AGAINST EGRESS. |
| |
| PER NFPA 101, CHAPTER 42, STORAGE OCCUPANCIES |
| |
| 42.2 MEANS OF EGRESS REQUIREMENTS. |
| 42.2.1 GENERAL. |
| 42.2.1.1 EACH REQUIRED MEANS OF EGRESS SHALL BE IN |
| ACCORDANCE WITH THE APPLICABLE PORTIONS OF CHAPTER 7. |
| |
| 42.2.2 MEANS OF EGRESS COMPONENTS. |
| 42.2.2.2 DOORS. |
| 42.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE |
| PERMITTED. |
| |
| 7.2.1.4.2 DOOR LEAF SWING DIRECTION. DOOR LEAVES |
| REQUIRED TO BE OF THE SIDE-HINGED OR PIVOTED-SWINGING |
| TYPE SHALL SWING IN THE DIRECTION OF EGRESS TRAVEL |
| UNDER ANY OF THE FOLLOWING CONDITIONS: |
| (1) WHERE SERVING A ROOM OR AREA WITH AN OCCUPANT LOAD |
| OF 50 OR MORE, EXCEPT UNDER ANY OF THE FOLLOWING |
| CONDITIONS: |
| (A) DOOR LEAVES IN HORIZONTAL EXITS SHALL NOT BE |
| REQUIRED TO SWING IN THE DIRECTION OF EGRESS TRAVEL |
| WHERE PERMITTED BY 7.2.4.3.8.1 OR 7.2.4.3.8.2. |
| (B) DOOR LEAVES IN SMOKE BARRIERS SHALL NOT BE REQUIRED |
| TO SWING IN THE DIRECTION OF EGRESS TRAVEL IN EXISTING |
| HEALTH CARE OCCUPANCIES, AS PROVIDED IN CHAPTER 19. |
| (2) WHERE THE DOOR ASSEMBLY IS USED IN AN EXIT |
| ENCLOSURE, UNLESS THE DOOR OPENING SERVES AN INDIVIDUAL |
| LIVING UNIT THAT OPENS DIRECTLY INTO AN EXIT ENCLOSURE |
| (3) WHERE THE DOOR OPENING SERVES A HIGH HAZARD |
| CONTENTS AREA |
| |
| PLEASE REVIEW AND CORRECT THE SWING OR JUSTIFY THEY ARE |
| NOT REQUIRED FOR EXIT AND REMOVE THE EXIT SIGNS. |
| |
| |
| |
| |
| 2) SHEET A 203 - PALLET STORAGE IS INDICATED, BUIT NO |
| DETAIL IS PROVIDED. |
| |
| PLEASE PROVIDE DETAILS OF THE PROPOSED PALLET SYSTEM |
| AND COMMODITY CLASSIFICATION PER NFPA 101. CHAPTER 6, |
| CLASSIFICATION OF OCCUPANCY AND HAZARD OF CONTENTS |
| |
| 6.2 HAZARD OF CONTENTS. |
| |
| 6.2.2 CLASSIFICATION OF HAZARD OF CONTENTS. |
| 6.2.2.1* GENERAL. THE HAZARD OF CONTENTS OF ANY |
| BUILDING OR STRUCTURE SHALL BE CLASSIFIED AS LOW, |
| ORDINARY, OR HIGH IN ACCORDANCE WITH 6.2.2.2, 6.2.2.3, |
| AND 6.2.2.4. |
| |
| PLEASE PROVIDE DETAILS. |
| |
| |
| |
| 3) SHEET A 203 - RACK STORAGE IS INDICATED, BUT NO |
| DETAIL IS PROVIDED. THOUGH A SEPARATE PERMIT IS |
| INDICATED, RACK INFORMATION SHALL BE SUBMITTED FOR |
| INFORMATIONAL PURPOSES TO CONDUCT A PLAN REVIEW. |
| |
| PLEASE PROVIDE DETAILS ON THE SIZE, HEIGHT, AND TYPE OF |
| RACKS AND WHAT WILL BE STORED ON THEM. |
| |
| |
| |
| |
| 4) SHEET A 203 - A FIRE SPRINKLER SYSTEM IS INDICATED. |
| IS THIS A NEW SYSTEM OR AN EXISTING ONE. |
| |
| PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, |
| FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE |
| POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF |
| APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, |
| CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR |
| AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER |
| SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) |
| AND ANY PERFORMANCE BASED INFORMATION SUCH AS |
| PRE-ENGINEERED SYSTEMS. |
| |
| 61G15-32.003 COMMON REQUIREMENTS TO ALL FIRE PROTECTION |
| ENGINEERING |
| DOCUMENTS. |
| (1) THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS |
| SHALL PROVIDE THE ENGINEERING REQUIREMENTS TO BE USED |
| IN THE PREPARATION OF THE FIRE PROTECTION SYSTEM LAYOUT |
| DOCUMENTS AND TO INDICATE THE NATURE AND SCOPE OF THE |
| WORK, AND TO DESCRIBE, DETAIL, DIMENSION, LABEL AND |
| DEFINE THE FIRE PROTECTION COMPONENTS, SYSTEM(S), |
| MATERIALS, ASSEMBLIES, EQUIPMENT AND ITS STRUCTURAL AND |
| UTILITY SUPPORT SYSTEM(S), INSOFAR AS THEY INVOLVE THE |
| SAFEGUARDING OF LIFE, HEALTH OR PROPERTY. |
| (2) THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS |
| SHALL SPECIFY THE APPLICABLE REQUIREMENTS FOR THE |
| ACCEPTANCE TESTING OF THE FIRE PROTECTION SYSTEM AND |
| COMPONENTS, WHICH SHALL BE BASED UPON APPLICABLE CODES |
| AND STANDARDS, WHERE AVAILABLE. |
| (3) THE OCCUPANCY OF THE AREA OR DESCRIPTION OF A |
| SPECIFIC HAZARD BEING PROTECTED BY THE FIRE PROTECTION |
| SYSTEM(S) SHALL BE SHOWN ON THE FIRE PROTECTION SYSTEM |
| ENGINEERING DOCUMENTS. |
| (4) THE APPLICABLE CODE AND STANDARD TO BE USED IN THE |
| PREPARATION OF THE FIRE PROTECTION SYSTEM LAYOUT |
| DOCUMENTS SHALL BE SHOWN ON THE FIRE PROTECTION SYSTEM |
| ENGINEERING DOCUMENTS. WHEN CODES AND STANDARDS ARE NOT |
| AVAILABLE OR APPLICABLE, AND SAID LAYOUT DOCUMENTS ARE |
| TO BE BASED ON ENGINEERING JUDGMENT, ANY REASONS AND |
| ASSUMPTIONS MADE TO DEVELOP THE FIRE PROTECTION CONCEPT |
| SHALL BE IDENTIFIED ON THE FIRE PROTECTION SYSTEM |
| ENGINEERING DOCUMENTS. |
| (5) STRUCTURAL SUPPORT AND STRUCTURAL OPENINGS REQUIRED |
| BY THE FIRE PROTECTION SYSTEM SHALL BE SHOWN ON THE |
| FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS AND SHALL |
| BE REFERENCED ON STRUCTURAL ENGINEERING DOCUMENTS. |
| (6) WHEN LAYOUT DOCUMENTS CONTAIN MATERIAL DEVIATION |
| FROM THE ENGINEER OF RECORD'S FIRE PROTECTION SYSTEM |
| ENGINEERING DOCUMENT, SUCH LAYOUT DOCUMENTS ARE NOT |
| COMPLIANT UNLESS THEY ARE ACCOMPANIED BY REVISED |
| ENGINEERING DOCUMENTS MADE AND SEALED BY THE ENGINEER |
| OF RECORD FOR THE FIRE PROTECTION SYSTEM. |
| (7) REQUIREMENTS FOR ACTIVATION CONTROL SYSTEMS, |
| SEQUENCE, OPERATING PARAMETERS, INTERLOCKS, SAFETY |
| RELATED DEVICES, INDICATORS AND ALARMS, SHALL BE SHOWN |
| ON THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS, |
| UNLESS SHOWN ON OTHER RELATED DOCUMENTS. |
| (8) ANY INFORMATION DEEMED APPROPRIATE BY THE ENGINEER |
| OF RECORD TO ASSIST THE AUTHORITY HAVING JURISDICTION |
| IN UNDERSTANDING THE OWNER?S INTENDED USE AND PROPOSED |
| PROTECTION OF THE BUILDING OR FACILITY AND TO PROVIDE |
| SUFFICIENT DIRECTION TO THE INSTALLATION CONTRACTOR OR |
| OTHER INTERESTED PARTIES REGARDING THE LAYOUT OF THE |
| SYSTEM(S), SHALL BE INCLUDED IN THE FIRE PROTECTION |
| SYSTEM ENGINEERING DOCUMENTS. |
| SPECIFIC AUTHORITY 471.008, 471.033(2), FS |
| LAW IMPLEMENTED 471.005(7), 471.033(2), FS |
| HISTORY?NEW 5-19-93, FORMERLY 21H-32.003, AMENDED |
| 4-2-2000, 6-26-01 |
| |
| 61G15-32.004 DESIGN OF WATER BASED FIRE PROTECTION |
| SYSTEMS. |
| (1) WATER BASED FIRE PROTECTION SYSTEMS INCLUDE, BUT |
| ARE NOT LIMITED TO, AUTOMATIC SPRINKLER SYSTEMS OF WET, |
| DRY, FINE WATER SPRAY (MIST), MANUAL, AND DELUGE VALVE |
| CONTROLLED TYPES, PUMPING SYSTEMS, STANDPIPES, FIRE |
| WATER MAINS AND DEDICATED FIRE PROTECTION WATER |
| SOURCES. |
| (2) TO ENSURE MINIMUM DESIGN QUALITY IN FIRE PROTECTION |
| SYSTEM ENGINEERING DOCUMENTS, SAID DOCUMENTS SHALL |
| INCLUDE AS A MINIMUM THE FOLLOWING INFORMATION WHEN |
| APPLICABLE: |
| (A) THE POINT OF SERVICE FOR THE FIRE PROTECTION WATER |
| SUPPLY AS DEFINED BY 633.021(18) F.S. |
| (B) APPLICABLE NFPA STANDARD TO BE APPLIED, OR IN THE |
| CASE WHERE NO SUCH STANDARD EXISTS, THE ENGINEERING |
| STUDY, JUDGMENTS, AND/OR PERFORMANCE BASED ANALYSIS AND |
| CONCLUSIONS. |
| (C) CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR |
| AREA. |
| (D) DESIGN APPROACH, WHICH INCLUDES SYSTEM TYPE, |
| DENSITIES, DEVICE TEMPERATURE RATING, AND SPACING FOR |
| EACH SEPARATE 42 HAZARD OCCUPANCY. |
| (E) CHARACTERISTICS OF WATER SUPPLY TO BE USED, SUCH AS |
| MAIN SIZE AND LOCATION, WHETHER IT IS DEAD-END OR |
| CIRCULATING; AND IF DEAD-END, THE DISTANCE TO THE |
| NEAREST CIRCULATING MAIN, AS WELL AS ITS MINIMUM |
| DURATION AND RELIABILITY FOR THE MOST HYDRAULICALLY |
| DEMANDING DESIGN AREA. |
| (F) WHEN PRIVATE OR PUBLIC WATER SUPPLIES ARE USED, THE |
| FLOW TEST DATA, INCLUDING DATE AND TIME OF TEST, WHO |
| CONDUCTED TEST OR SUPPLIED INFORMATION, TEST ELEVATION, |
| STATIC GAUGE PRESSURE AT NO FLOW, FLOW RATE WITH |
| RESIDUAL GAUGE PRESSURE, HYDRANT BUTT COEFFICIENT, AND |
| LOCATION OF TEST IN RELATION TO THE HYDRAULIC POINT OF |
| SERVICE. |
| (G) VALVING AND ALARM REQUIREMENTS TO MINIMIZE |
| POTENTIAL FOR IMPAIRMENTS AND UNRECOGNIZED FLOW OF |
| WATER. |
| (H) MICROBIAL INDUCED CORROSION (MIC). THE ENGINEER OF |
| RECORD SHALL MAKE REASONABLE EFFORTS TO IDENTIFY WATER |
| SUPPLIES THAT COULD LEAD TO MICROBIAL INDUCED CORROSION |
| (MIC). SUCH EFFORTS MAY CONSIST OF DISCUSSIONS WITH THE |
| LOCAL WATER PURVEYOR AND/OR FIRE OFFICIAL, FAMILIARITY |
| WITH CONDITIONS IN THE LOCAL AREA, OR LABORATORY |
| TESTING OF WATER SUPPLIES. WHEN CONDITIONS ARE FOUND |
| THAT MAY RESULT IN MIC CONTAMINATION OF THE FIRE |
| PROTECTION PIPING, THE ENGINEER SHALL DESIGN CORRECTIVE |
| MEASURES. |
| (I) BACKFLOW PREVENTION AND METERING SPECIFICATIONS AND |
| DETAILS TO MEET LOCAL WATER PURVEYOR REQUIREMENTS |
| INCLUDING MAXIMUM ALLOWABLE PRESSURE DROP. |
| (J) QUALITY AND PERFORMANCE SPECIFICATIONS OF ALL YARD |
| AND INTERIOR FIRE PROTECTION COMPONENTS. |
| (3) CONTRACTOR SUBMITTALS WHICH DEVIATE FROM THE ABOVE |
| MINIMUM DESIGN PARAMETERS SHALL BE CONSIDERED MATERIAL |
| DEVIATIONS AND REQUIRE SUPPLEMENTAL ENGINEERING |
| APPROVAL AND DOCUMENTATION. |
| (4) IN THE EVENT THE ENGINEER OF RECORD PROVIDES MORE |
| INFORMATION AND DIRECTION THAN IS ESTABLISHED ABOVE, HE |
| OR SHE SHALL BE HELD RESPONSIBLE FOR THE TECHNICAL |
| ACCURACY OF THE WORK IN ACCORDANCE WITH APPLICABLE |
| CODES, STANDARDS, AND SOUND ENGINEERING PRINCIPLES. |
| SPECIFIC AUTHORITY 471.008, 471.033(2), FS |
| LAW IMPLEMENTED 471.005(7), 471.033(2), FS |
| HISTORY?NEW 5-19-93, FORMERLY 21H-32.004, AMENDED |
| 4-2-2000, 6-26-01, 7-12-05 |
| |
| |
| PLEASE PROVIDE THE REQUIRED FIRE SPPRINKLER DOCUMENTS |
| IN DRAWING OR NARRATIVE FORM FOR THIS MASTER PERMIT. |
| SHOP DRAWINGS SHALL BE PREPARED OFF OF THESE CRITERIA |
| AND SUBMITTED AT A LATER DATE. |
| |
| |
| |
| |
| 5) SHEET 3.1 - THERE ARE NO INDICATIONS OF EXIT SIGNS |
| IN THE AISLES OF THE WAREHOUSE AREAS. EXIT SIGNS MAY BE |
| REQUIRED IF YOU CAN NOT SEE THE ONES BY THE EXIT DOORS. |
| |
| 42.2.8 ILLUMINATION OF MEANS OF EGRESS. |
| |
| 42.2.8.1 MEANS OF EGRESS SHALL BE ILLUMINATED IN |
| ACCORDANCE WITH SECTION 7.8. |
| |
| 7.8 ILLUMINATION OF MEANS OF EGRESS. |
| 7.8.1 GENERAL. |
| 7.8.1.1* ILLUMINATION OF MEANS OF EGRESS SHALL BE |
| PROVIDED IN ACCORDANCE WITH SECTION 7.8 FOR EVERY |
| BUILDING AND STRUCTURE WHERE REQUIRED IN CHAPTERS 11 |
| THROUGH 43. FOR THE PURPOSES OF THIS REQUIREMENT, EXIT |
| ACCESS SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES, |
| CORRIDORS, RAMPS, ESCALATORS, AND PASSAGEWAYS LEADING |
| TO AN EXIT. FOR THE PURPOSES OF THIS REQUIREMENT, EXIT |
| DISCHARGE SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES, |
| CORRIDORS, RAMPS, ESCALATORS, WALKWAYS, AND EXIT |
| PASSAGEWAYS LEADING TO A PUBLIC WAY. |
| 7.8.1.2 ILLUMINATION OF MEANS OF EGRESS SHALL BE |
| CONTINUOUS DURING THE TIME THAT THE CONDITIONS OF |
| OCCUPANCY REQUIRE THAT THE MEANS OF EGRESS BE AVAILABLE |
| FOR USE, UNLESS OTHERWISE PROVIDED IN 7.8.1.2.2. |
| |
| PLEASE REIVEW AND CORRECT. |
| |
| |
| |
| 6) SHEET E 0.1 - THERE IS NO INDICATIONS OF A FIRE |
| ALARM SYSTEM. |
| |
| 9.6 FIRE DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS. |
| 9.6.1* GENERAL. |
| 9.6.1.1 THE PROVISIONS OF SECTION 9.6 SHALL APPLY ONLY |
| WHERE SPECIFICALLY REQUIRED BY ANOTHER SECTION OF THIS |
| CODE OR WHERE SUPERVISION OF A NEW FIRE SPRINKLER |
| SYSTEM OR NEW FIRE ALARM SYSTEM IS REQUIRED BY THE |
| FLORIDA BUILDING CODE. |
| |
| 9.7.1.4 AUTOMATIC SPRINKLER SYSTEMS INSTALLED TO MAKE |
| USE OF AN ALTERNATIVE PERMITTED BY THIS CODE SHALL BE |
| CONSIDERED REQUIRED SYSTEMS AND SHALL MEET THE |
| PROVISIONS OF THIS CODE THAT APPLY TO REQUIRED SYSTEMS. |
| |
| A FIRE SPRINKLER IS REQUIRED AND SHALL BE MONITORED. |
| ALL FIRE ALARM WORK SHALL BE DONE UNDER SEPARATE SHOP |
| DRAWINGS BY CERTIFIED LIFE SAFETY CONTRACTORS. |
| |
| PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE. |
| |
| |
| 7) INFORMATIONAL PURPOSES - SHOULD # 2 ABOVE FIND THE |
| THE HAZARD CLASSIFICATION AS HIGH HAZARD THEN THE |
| FOLLOWING SHALL APPLY. |
| |
| 42.2.4.3 AREAS WITH HIGH HAZARD CONTENTS SHALL COMPLY |
| WITH SECTION 7.11. |
| |
| 7.11 SPECIAL PROVISIONS FOR OCCUPANCIES WITH HIGH |
| HAZARD |
| CONTENTS. SEE SECTION 6.2. |
| 7.11.1* WHERE THE CONTENTS ARE CLASSIFIED AS HIGH |
| HAZARD, EXITS SHALL BE PROVIDED AND ARRANGED TO ALLOW |
| ALL OCCUPANTS TO ESCAPE FROM THE BUILDING OR STRUCTURE, |
| OR FROM THE HAZARDOUS AREA THEREOF, TO THE OUTSIDE OR |
| TO A PLACE OF SAFETY WITH A TRAVEL DISTANCE OF NOT MORE |
| THAN 75 FT (23 M), MEASURED AS REQUIRED IN 7.6.1, |
| UNLESS OTHERWISE PROVIDED IN 7.11.2 |
| |
| PLEASE REVIEW AND PROVIDE FOR CORRECTIONS. |
| |
| |
| |
| |
| 8) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| |
| 9) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |